beautypg.com

6 single duct with radiator or floor heating, Single duct – Siemens RDG400 User Manual

Page 21

background image

21 / 42

Siemens

RDG100, RDG100T, RDG110, RDG140, RDG160 Basic Documentation

CE1P3182en

Building Technologies

Functions

28 May 2009

4.7.6

Single duct with radiator or floor heating

In single duct applications with radiator or floor heating, the thermostat controls a
valve plus an auxiliary electrical heater. Parameter P01 is not available.

The output signal for the air flow can be limited to a minimum and maximum value
if required (see section 4.6 "additional features").


The air flow starts to rise when the acquired room temperature is above "setpoint"
+ "dead zone".
The radiator receives an ON command when the acquired room temperature drops
below “setpoint” – “dead zone” (= “setpoint for radiator”).

Note: “Setpoint for radiator” is limited by parameter “Maximum heating setpoint”
(P10).


The radiator sequence can also be used for floor heating.
The "Floor heating limitation function" is described on page 15.


ON/OFF radiator / floor heating

Modulating radiator / floor heating

Y

YR

TR [°C]

dz

ma

x

mi

n

Y

0%

100%

TR [°C]

XpC

YV

C

Vmin

Vmax

ON

OFF

W

SDH

Y

0%

100%

YR

TR [°C]

XpH

W

dz

ma

x

mi

n

Y

0%

100%

TR [°C]

XpC

YV

C

Vmin

Vmax

Y Output

signal

TR Room

temperature

W

Effective setpoint Comfort

H Heating

sequence

C Cooling

sequence

YV

Volume flow rate

YR

Radiator / floor heating

XpH

Proportional band heating

XpC

Proportional band cooling

Vmin Minimum volume output
Vmax Maximum volume output


Note: The diagrams show the PI controller's proportional part only.

Setting the sequence and the control outputs

Refer to sections 4.5 (applications), 4.7.1 (sequences) and 4.7.3 (outputs).

Floor heating

Sequences