Siemens

RDG100, RDG100T, RDG110, RDG140, RDG160 Basic Documentation

CE1P3182en

Building Technologies

Engineering

28 May 2009

6 Engineering

6.1

Connection terminals

G X1 M X2 D1 GND

G0

SELV

G, G0 Operating voltage AC 24 V

Y10/G0 Control output for DC 0…10 V actuator

Y1/G, Y2/G Control output for 2-position, PWM or 3-position actuators

X1, X2 Multifunctional input for temperature sensor (e.g. QAH11.1)

or potential-free switch

Factory setting:

- X1 = external room temperature sensor

- X2 = sensor or switch for automatic heating / cooling

changeover

M

Measuring neutral for sensor and switch

D1, GND Multifunctional input for potential-free switch.

Factory setting: Operating mode switchover contact