beautypg.com

5 applications overview, Position – Siemens RDG400 User Manual

Page 13

background image

13 / 42

Siemens

RDG100, RDG100T, RDG110, RDG140, RDG160 Basic Documentation

CE1P3182en

Building Technologies

Functions

28 May 2009

4.5

Applications overview

The thermostat supports the following applications, which can be configured via
DIP switches
at the rear of the unit. The control output for the damper actuator is
either DC 0…10 V (factory setting) or 3-position (see parameter P47), and for the
heating / cooling output ON/OFF, PWM, 3-position or DC 0…10 V.

Application

DIP switch

Control output

DC 0…10 V

Single-duct

• DC 0…10 V damper actuator
• 3-position damper actuator

YV

T

B1

M

V

1 2 3 4 5

ON

OFF

3-position

DC 0…10 V

Single-duct with electrical heater

• DC 0…10 V damper actuator and

ON/OFF, PWM or 3-position electrical
heater

• 3-position damper actuator and

DC 0…10 V electrical heater

YV

YE

M

V

T

B1

1 2 3 4 5

ON

OFF

ON/OFF, PWM or
3-position

DC 0…10 V

Single-duct and radiator / floor
heating

• DC 0…10 V damper actuator and

ON/OFF, PWM or 3-position radiator

• 3-position damper actuator and

DC 0…10 V radiator

YR

YV

T

B1

1 2 3 4 5

ON

OFF

ON/OFF, PWM or
3-position

DC 0…10 V

Single-duct heating / cooling coil

• DC 0…10 V damper actuator and

ON/OFF, PWM or 3-position heating /
cooling

• 3-position damper actuator and

DC 0…10 V heating /cooling

YV

M

V

Y1

T

B2

T

B1

1 2 3 4 5

ON

OFF

ON/OFF, PWM or
3-position


Key

Y1 Heating or heating/cooling valve actuator B1 Return air temperature sensor or external

room temperature sensor (optional)

YV damper actuator

B2 Changeover sensor (optional)

YE

Electrical

heater