2 parameters expert level, diagnostics & test, Control parameters – Siemens RDG400 User Manual
Page 30
30 / 42
Siemens
RDG100…/RDG110…/RDG140.../RDG160… Basic Documentation
CE1P3182en
Building Technologies
Functions
28 May 2009
4.12.2 Parameters Expert level, diagnostics & test
Pa
ra
me
te
r
Name
Factory setting
Range
RDG400
Expert level
P30
P-band / Switching differential in heating mode
2 K
0.5 … 6 K
P31
P-band / Switching differential in cooling mode
1 K
0.5 … 6 K
P32
P-band / Switching differential for radiator
2 K
0.5 … 6 K
P33
Dead zone in Comfort mode
2 K
0.5 … 5 K
P34
Setpoint differential (w
D
)
2 K
0.5 … 5 K
P35
Integral time
5 min
0…10 min
P36
Heating / cooling changeover switching point
cooling (X1/X2)
16 °C
10…25 °C
P37
Heating / cooling changeover switching point
heating (X1/X2)
28 °C
27…40 °C
P38
Functionality of X1
1: = Ext. sensor
0 = --- (no function)
1 = Room temp ext / Return temp (AI)
2 = H/C changeover (AI/DI)
3 = Operating mode contact [DI)
4 = Dew point sen. (DI)
5 = Enable electric heater (DI)
6 = Fault input (DI)
0..6
P39
Operating action of X1 if digital input
0 (N.O.)
0 = Normally open / Open
1 = Normally closed / Closed
P40
Functionality of X2
2 = H/C changeover 0 = --- (no function)
1 = Room temp ext / Return temp (AI)
2 = H/C changeover (AI/DI)
3 = Operating mode contact [DI)
4 = Dew point sen. (DI)
5 = Enable electric heater (DI)
6 = Fault input (DI)
0..6
P41
Operating action of X2 if digital input
0 (N.O.)
0 = Normally open / Open
1 = Normally closed / Closed
P42
Functionality of D1
3 = Op. mode
changeover
0 = --- (no function)
2 = H/C changeover (DI)
3 = Operating mode contact [DI)
4 = Dew point sen. (DI)
5 = Enable electric heater (DI)
6 = Fault input (DI)
0..6
P43
Operating action of D1 if digital input
0 (N.O.)
0 = Normally open / Open
1 = Normally closed / Closed
P44
Running time of Y1/Y2 output
(only when modulating PI control)
150 s
20…300 sec
P46
Output Y1/Y2 (if not parameterized as 3-pos.)
ON/OFF (1)
1 = 2-position
2 = PWM
P51
Floor heating limit temperature
OFF
OFF, 10..50 °C
P63
Minimum output limitation air flow signal
0%
0…P64 (%)
P64
Maximum output limitation air flow signal
100%
P63…100 (%)
P65
Protection heating setpoint
8 °C
OFF, 5 … W Cool Prot;
(W Cool Prot = 40 °C max)
P66
Protection cooling setpoint
OFF
OFF, W Heat Prot … 40;
(W Heat Prot = 5 °C min.)
P68
Prolong Comfort period
OFF
OFF; 15 ... 360 min
P69
Temporary setpoint Comfort
(see also Comfort setpoint P08)
OFF
OFF = Disabled
ON = Enable
P71
Reload factory settings
OFF
OFF = Disabled
ON = Reload start
P46: Setting to 2-position or 3-position is done with DIP 4
Note