beautypg.com

State Industries GS675YRVIT User Manual

Page 10

background image

10

Minimum clearances between the water heater and combustible

construction are 0 inch at the sides and rear, 5.5” (14.0 cm) from the

front and 12” (30.5 cm) from the top (standard clearance). If clearances

stated on the heater differ from standard clearances, install water

heater according to clearances stated on the heater.
Adequate clearance 24” (61.0 cm) for servicing this appliance should

be considered before installation, such as changing the anodes, etc.
A minimum clearance of 5.5” (14.0 cm) must be allowed for access to

replaceable parts such as the thermostats, drain valve and relief valve.
When installing the heater, consideration must be given to proper

location. Location selected should be as close to the wall as practicable

and as centralized with the water piping system as possible.

fIGure 3.

fIGure 4.

A gas water heater cannot operate properly without the correct amount

of air for combustion. Do not install in a confined area such as a closet,

unless you provide air as shown in the “Locating The New Water

Heater” section. Never obstruct the flow of ventilation air. If you have

any doubts or questions at all, call your gas supplier. Failure to provide

the proper amount of combustion air can result in a fire or explosion

and cause death, serious bodily injury, or property damage.

fIGure 5.

If this water heater will be used in beauty shops, barber shops, cleaning

establishments, or self-service laundries with dry cleaning equipment, it

is imperative that the water heater or water heaters be installed so that

combustion and ventilation air be taken from outside these areas.

Propellants of aerosol sprays and volatile compounds (cleaners,

chlorine based chemicals, refrigerants, etc.), in addition to being highly

flammable in many cases, will also react to form corrosive hydrochloric

acid when exposed to the combustion products of the water heater.

The results can be hazardous, and can also cause product failure.

InsulatIon BlanKets

Insulation blankets are available to the general public for external use

on gas water heaters but are not necessary with these products. The

purpose of an insulation blanket is to reduce the standby heat loss

encountered with storage tank heaters. Your water heater meets or

exceeds the Energy Policy Act standards with respect to insulation and

standby loss requirements, making an insulation blanket unnecessary.
Should you choose to apply an insulation blanket to this heater, you

should follow these instructions (for identification of components

mentioned below, see Figure 1). Failure to follow these instructions

can restrict the air flow required for proper combustion, potentially

resulting in fire, asphyxiation, serious personal injury, or death.

• Do not apply insulation to the top of the water heater, as this will

interfere with safe operation of the blower assembly.

• Do not cover outer door, thermostat or temperature & pressure relief valve.

• Do not allow insulation to come within 2” (5.1 cm) of the floor to

prevent blockage of combustion air flow to the burner.

• Do not cover the instruction manual. Keep it on the side of the

water heater or nearby for future reference.

• Do obtain new warning and instruction labels from the manufacturer

for placement on the blanket directly over the existing labels.

• Do inspect the insulation blanket frequently to make certain it

does not sag, thereby obstructing combustion air flow.

coMBustIon aIr and ventIlatIon for

applIances located In unconfIned spaces

unconfIned space is space whose volume is not less than

50 cubic feet per 1,000 Btu per hour (4.8 cubic meters per kW) of the aggregate

input rating of all appliances installed in that space. Rooms communicating

directly with the space in which the appliances are installed, through openings

not furnished with doors, are considered a part of the unconfined space.
In unconfined spaces in buildings, infiltration may be adequate to

provide air for combustion, ventilation and dilution of flue gases.

However, in buildings of tight construction (for example, weather

stripping, heavily insulated, caulked, vapor barrier, etc.), additional air

may need to be provided using the methods described in “Combustion

Air and Ventilation for Appliances Located in Confined Spaces.”

coMBustIon aIr and ventIlatIon for

applIances located In confIned spaces

confIned space is a space whose volume is less than 50 cubic

feet per 1,000 Btu per hour (4.8 cm per kW) of the aggregate input

rating of all appliances installed in that space.
When drawing combustion air from inside a conventionally

constructed building to a confined space, such a space should be

provided with two permanent openings. ONE WITHIN 12 INCHES

(30 cm) OF THE ENCLOSURE TOP AND ONE WITHIN 12 INCHES

(30 cm) OF THE ENCLOSURE BOTTOM. Each opening should have

a free area of one square inch per 1000 Btu/hr (22 cm

2

/kW) of the

total input of all appliances in the enclosure, but not less than 100

square inches (645 cm

2

). If the confined space is within a building of

tight construction, air for combustion and ventilation must be obtained

from outdoors. When directly communicating with the outdoors or

communicating through vertical ducts, two permanent openings,

This manual is related to the following products: