JADE

ECONOMIZER MODULE

62-0331—11

6

Fig. 4. Economizer with Sylk Bus sensors for enthalpy configuration with Honeywell M7215 black motor.

S-BUS
S-BUS

OUTSIDE AIR

TEMP/HUMIDITY (ENTHALPY)

SYLKBUS SENSOR

RETURN AIR

TEMP/HUMIDITY (ENTHALPY)

SYLKBUS SENSOR

ROOF TOP UNIT

Y1O

Y2O
Y1I

Y2I

OCC

E-GND

Y1

G

W2

W1

Y2

O/B

OCC

W7220 ECONOMIZER CONTROLLER MODULE

THERMOSTAT

MAT

MAT

C R

R(+)

C(-)

M32565D

IN THIS CONFIGURATION, AN OPTIONAL DISCHARGE AIR TEMP/HUMIDITY

(ENTHALPY) SYLKBUS SENSOR CAN BE ADDED FOR ADVANCED CONTROL

AS SHOWN IN THE LOWER LEFT OF THIS FIGURE.

DO NOT USE THE C7250 20K NTC SENSOR WITH THE OA TERMINAL IN THIS

CONFIGURATION.

WHEN USING A HEAT PUMP THERMOSTAT, THERMOSTAT TERMINALS

MAY DIFFER: W1 MAY BE LABELED O OR B AND W2 MAY BE LABELED W.

WHEN USING A HEAT PUMP WITH DEFROST FEEDBACK, ADD AN ISOLATION

RELAY BETWEEN O AND C.

1

4

1

2

CO2

SENSOR

2-10 VDC

(OPTIONAL)

IAQ (2-10V)

IAQ COM

IAQ 24V

ACT (2-10V)

ACT COM

ACT 24V

+

-

TR1

TR

IN

IN

M7215

MA TEMP

SENSOR

20K NTC

AUX1-0

AUX2-I

3

2

4

3

1K1

1K1

24 VAC