ECONOMIZER MODULE
62-0331—11
12
SETPOINTS MAT SET
53ºF
38 to 70 ºF;
increment by 1
The economizer will modulate the OA damper to maintain the
mixed air temperature at the setpoint.
LOW T LOCK
32ºF
-45 to 80 ºF;
increment by 1
Setpoint determines outdoor temperature when the mechanical
cooling cannot be turned on. Commonly referred to as the
Compressor lockout. At or below the setpoint the Y1-O and
Y2-O will not be energized on the controller.
DRYBLB SET
63ºF
48 to 80 ºF;
increment by 1
Setpoint determines where the economizer will assume outdoor
air temperature is good for free cooling; e.g.; at 63 ºF setpoint
unit will economizer at 62 ºF and below and not economize at
64 ºF and above. There is a a 2 ºF deadband.
ENTH CURVE
ES3
ES1, ES2, ES3,
ES4, or ES5
Enthalpy boundary “curves” for economizing using single
enthalpy.
See page 22 for description of enthalpy curves.
DCV SET
1100ppm
500 to 2000
ppm
increment by
100
Displays ONLY if a CO2 sensor is connected.
Setpoint for Demand Control Ventilation of space. Above the
setpoint, the OA dampers will modulate open to bring in
additional OA to maintain a space ppm level below the setpoint.
MIN POS
2.8 V
2 to 10 Vdc
Displays ONLY if a CO2 sensor is NOT connected. With 2-speed
fan units MIN POS L (low speed fan) and MIN POS H (high
speed fan) settings are required. Default for MIN POS L is 3.2V
and MIN POS H is 2.8V.
VENTMAX
2.8 V
2 to 10 Vdc
or
100 to 9990 cfm
increment by 10
Displays only if a CO2 sensor is connected.
Used for Vbz (ventilation max cfm) setpoint. VENTMAX is the
same setting as MIN POS would be if you did not have the CO2
sensor.
Displays 2 to 10 V if <3 sensors (RA,OA and MA).
In DCV CAL ENABLE AUTO mode dampers controlled by CFM
With 2-speed fan units VENTMAX L (low speed fan) and
VENTMAX H (high speed fan) settings are required. Default for
VENTMAX L is 3.2V and VENTMAX H is 2.8V.
VENTMIN
2.25 V
2 to 10 Vdc
or
100 to 9990 cfm
increment by 10
Displays only if CO2 sensor is connected.
Used for Va (ventilation min cfm) setpoint. This is the ventilation
for less than maximum occupancy of the space.
Displays 2 to 10 V if <3 sensors (RA,OA and MA). Va is only set
if DCV is used.
In DCV CAL ENABLE AUTO mode dampers controlled by CFM
With 2-speed fan units VENTMIN L (low speed fan) and
VENTMIN H (high speed fan) settings are required. Default for
VENTMIN L is 2.5V and VENTMIN H is 2.25V.
ERV OAT SP
d
32ºF
0 to 50 ºF;
increment by 1
Only when AUX1 O = ERV
EXH1 SET
50%
0 to 100%;
increment by 1
Setpoint for OA damper position when exhaust fan 1 is powered
by the economizer.
With 2-speed fan units Exh1 L (low speed fan) and Exh1 H (high
speed fan) settings are required. Default for Exh1 L is 65% and
Exh1 H is 50%
EXH2 SET
75%
0 to 100%;
increment by 1
Setpoint for OA damper position when exhaust fan 2 is powered
by the economizer. Only used when AUX1 O is set to EHX2.
With 2-speed fan units Exh2 L (low speed fan) and Exh2 H (high
speed fan) settings are required. Default for Exh2 L is 80% and
Exh2 H is 75%
Table 4. Menu Structure
a
. (Continued)
Menu
Parameter
Parameter
Default
Value
Parameter
Range and
Increment
b
Notes