Menu structure, Setup and configuration, Using the keypad with settings and parameters – Jade Range W7220 User Manual
Page 10

JADE
™
ECONOMIZER MODULE
62-0331—11
10
Using the Keypad with Settings and
Parameters
To use the keypad when working with Setpoints, System and
Advanced Settings, Checkout tests, and Alarms:
• Navigate to the desired menu.
• Press the button (Enter) to display the first item in the
currently displayed menu.
• Use the
and
buttons to scroll to the desired
parameter.
• Press the button (Enter) to display the value of the
currently displayed item.
• Press the
button to increase (change) the displayed
parameter value.
a
• Press the
button to decrease (change) the displayed
parameter value.
a
• Press the button to accept the displayed value and store
it in non-volatile RAM.
• CHANGE STORED displays.
• Press the button (Enter) to return to the current menu
parameter.
• Press the
button (MenuUp/Exit) to return to the
previous menu.
a
When values are displayed, pressing and holding the
or
button causes the display to automatically
increment.
Menu Structure
Table 4 on page 10 illustrates the complete hierarchy of
menus and parameters for the JADE™ Economizer system.
The Menus in display order are:
• STATUS
• SETPOINTS
• SYSTEM SETUP
• ADVANCED SETUP
• CHECKOUT
• ALARMS
IMPORTANT
Table 4 on page 10 illustrates the complete hierarchy.
Your menu parameters will be different depending on
your configuration.
For example if you do not have a DCV (CO
2
) sensor,
then none of the DCV parameters appear and only
MIN POS will display. If you have a CO2 sensor, the
DCV MIN and DCV MAX will appear AND if you have
2 speed fan DCV MIN (high and low speed) and DCV
MAX (high and low speed will appear).
SETUP AND CONFIGURATION
Before being placed into service, the JADE™ Economizer
module must be setup and configured for the installed system.
IMPORTANT
During setup, the Economizer module is live at all
times.
The setup process uses a hierarchical menu structure that is
easy to use. You press the
and
arrow buttons to move
forward and backward through the menus and press the
button to select and confirm setup item changes.
Table 4. Menu Structure
a
.
Menu
Parameter
Parameter
Default
Value
Parameter
Range and
Increment
b
Notes
STATUS
ECON AVAIL
NO
YES/NO
YES = economizing available; the system can use Outdoor Air for
free cooling when required.
ECONOMIZING
NO
YES/NO
YES = Outdoor Air being used for 1
st
stage cooling.
OCCUPIED
NO
YES/NO
YES = OCC signal received from space thermostat or unitary
controller.
YES = 24 Vac on terminal OCC
No = 0 Vac on terminal OCC.
HEAT PUMP
n/a
c
COOL
HEAT
Displays COOL or HEAT when system is set to heat pump (non-
conventional)
COOL Y1-IN
OFF
ON/OFF
Y1-I signal from space thermostat or unitary controller for
cooling stage 1.
ON = 24 Vac on term Y1-I
OFF = 0 Vac on term Y1-I
COOL Y1-OUT
OFF
ON/OFF
Cool Stage 1 Relay Output to mechanical cooling (Y1-OUT
terminal).