Jade Range W7220 User Manual
Page 14

JADE
™
ECONOMIZER MODULE
62-0331—11
14
ADVANCED
SETUP
MA LO SET
45ºF
35 to 55 ºF;
increment by 1º
Temp to activate Freeze Protection (close damper or modulate to
MIN POS if temp falls below set value)
FREEZE POS
CLO
CLO
MIN
Damper position when freeze protection is active (closed or MIN
POS).
CO2 ZERO
0ppm
0 to 500 ppm;
increment by 10
CO2 ppm level to match CO2 sensor start level.
CO2 SPAN
2000ppm
1000 to 3000
ppm;
increment by 50
CO2 ppm span to match CO2 sensor; e.g.; 500-1500 sensor
output would be 500 CO2 zero and 1000 CO2 span.
STG3 DLY
2.0h
0 min, 5 min, 15
min, then 15
min intervals.
Up to 4h or OFF
Delay after stage 2 for cool has been active. Turns on 2nd stage
of mechanical cooling when economizer is 1st stage call and
mechanical cooling is 2nd stage call. Allows three stages of
cooling, 1 economizer and 2 mechanical.
OFF = no Stage 3 cooling.
SD DMPR POS
CLO
CLO
OPN
Indicates shutdown signal from space thermostat or unitary
controller. When controller receives 24 Vac input on the SD
terminal in conventional mode, the OA damper will open if
programmed for OPN and OA damper will close if programmed
for CLO. All other controls, e.g., Y1-O, Y2-O, EXH1, etc. will shut
off.
DCVCAL ENA
MAN
MAN (manual)
AUTO
Turns on the DCV automatic control of the dampers. Resets
ventilation based on the RA, OA and MA sensor conditions.
Requires all sensors (RA, OA, MA and CO2).
This operation is not operable with a 2-speed fan unit.
MAT T CAL
0.0 F°
+/-2.5F°
Allows for the operator to adjust for an out of calibration
temperature sensor
OA T CAL
0.0F°
+/-2.5F°
Allows for the operator to adjust for an out of calibration
temperature sensor
OA H CAL
0% RH
+/-10% RH
Allows for the operator to adjust for an out of calibration
humidity sensor
RA T CAL
0.0F°
+/-2.5F°
Allows for the operator to adjust for an out of calibration
temperature sensor
RA H CAL
0% RH
+/-10% RH
Allows for the operator to adjust for an out of calibration
humidity sensor
DA T CAL
0.0 F°
+/-2.5F°
Allows for the operator to adjust for an out of calibration
temperature sensor
2SP FAN DELAY
5 Minutes 0 to 20 minutes
in 1 minute
increments.
When in economizing mode this is the delay for the high speed
fan to try to satisfy the call for second stage cooling before the
first stage mechanical cooling is enabled.
Table 4. Menu Structure
a
. (Continued)
Menu
Parameter
Parameter
Default
Value
Parameter
Range and
Increment
b
Notes