Jade Range W7220 User Manual
Page 13

JADE
™
ECONOMIZER MODULE
13
62-0331—11
SYSTEM
SETUP
INSTALL
01/01/11
Display order = MM/DD/YY
Setting order = DD, MM, then YY.
UNITS DEG
ºF
ºF or ºC
Sets economizer controller in degrees Fahrenheit or Celsius.
EQUIPMENT
CONV
CONV
HP
CONV = conventional.
HP O/B = Enables Heat Pump mode. Use AUX2 I for Heat Pump
input from thermostat or controller.
AUX2 I
n/a
Shutdown (SD)
Heat (W1)
HP(O)
HP(B)
In CONV mode:
SD = Enables configuration of shutdown (default);
W = Informs controller that system is in heating mode.
NOTE: If using 2-speed fan mode, you must pro-
gram CONV mode for W. Shutdown is not
available in the two-speed fan mode.
In HP O/B mode:
HP(O) = energize heat pump on Cool (default);
HP(B) = energize heat pump on Heat.
FAN SPEED
1 speed
1 speed/
2 speed
Sets economizer controller for operation of 1 speed or 2 speed
supply fan. The controller does not control the fan but positions
the OA and RA dampers to the heating or cooling mode. See
page 23 for modes and position.
NOTE: 2-speed fan option also needs Heat (W1) pro-
grammed in AUX 2 In.
FAN CFM
5000cfm
100 to 15000
cfm;
increment by
100
This is the capacity of the RTU. The value is found on the label
from the RTU manufacturer.
AUX1 OUT
NONE
NONE
ERV
EXH2
SYS
• NONE = not configured (output is not used)
• ERV= Energy Recovery Ventilator
d
• EXH2 = second damper position 24 Vac out for second
exhaust fan.
• SYS = use output as an alarm signal
OCC
INPUT
INPUT or
ALWAYS
When using a setback thermostat with occupancy out (24 Vac),
the 24 Vac is input “INPUT” to the OCC terminal. If no
occupancy output from the thermostat then change program to
“ALWAYS” OR add a jumper from terminal R to OCC terminal.
FACTORY DEFAULT
NO
NO or YES
Resets all set points to factory defaults when set to YES. LCD
will briefly flash YES and change to NO but all parameters will
change to factory default values.
Table 4. Menu Structure
a
. (Continued)
Menu
Parameter
Parameter
Default
Value
Parameter
Range and
Increment
b
Notes