beautypg.com

Cleaning and maintenance, Warning – Mastic Spark Modern Fires 91P User Manual

Page 34

background image

34

L100001

37

Figure 45 - Pilot Flame

Thermopile

Thermocouple

BURNER FLAME

The flames from the burner should be visually checked as
soon as the heater is installed and periodically during normal
operation. In normal operation, at full rate, and after operat-
ing for about 15 to 30 minutes, the flame should be yellow

and up to 8 inches high.

See Figure 46.

NOTE: The type of installation, vent system
configuration, and wind effects may cause the flame
patterns to vary.

AIR SHUTTER ASSEMBLY

Air shutter is adjusted at factory:

1

/

8

" for natural gas and

propane gas
If necessary, change this by loosening nut and opening or
closing the air shutter more. See Figure 47.

Figure 46 - Burner Flame Appearance

CLEANING AND MAINTENANCE

BURNER, PILOT AND CONTROL COMPARTMENT

Keep the control compartment and burner areas clean by vacuuming or brushing at least twice a year.
Make sure the burner porting, pilot air opening and burner air opening are free of obstructions at all times.
PILOT FLAME

The flames from the pilot should be visually checked as soon as the heater is installed
and periodically during normal operation. The pilot flame must always be present
when the fireplace is in operation.
See Figure 45. The pilot flame has three distinct
flames, one engulfing the thermopile, one engulfing the thermocouple, and the other
reaching to the main burner.

BURNER

Inspect area around the injector. Remove any lint or foreign material with a brush
or vacuum.

Turn off gas before servicing fireplace. It
is recommended that a qualified service
technician perform these check-ups at the
beginning of each heating season.

WARNING

Figure 47 - Adjusting Air Shutter

Nut

Shutter Opening

This manual is related to the following products: