beautypg.com

Vent installation, How to use the vent graph – Mastic Spark Modern Fires 91P User Manual

Page 16

background image

16

L100001

17

���� �������

���� �������

� � ����������� ����������

�������������� ����������

����������� �
��������������
� � ��� �������
� � ��� �������

� � ������� ����� �� ��� ��������

��� ������ ��������

� � ������� ����� ��� ���� ���� ��

������ ��������
����������� � ��� �������
�������������� � ��� �������

� � ��������� ���� ������ �� ������

��������
����������� � �� �������
�������������� � �� ������

������ ������

������ ��������

������� ������

������� ���� �� ���� ����

������� ���� �������������

���� ����

VENT INSTALLATION

TERMINATION CLEARANCES FOR BUILDINGS WITH COMBUSTIBLE
AND NONCOMBUSTIBLE EXTERIORS

Figure 9 - Allowable Venting Chart

HOW TO USE THE VENT GRAPH

The Vent Graph should be read in conjunction with the following
vent installation instructions to determine the relationship between
the vertical and horizontal dimensions of the vent system.
1. Determine the height of the center of the horizontal vent pipe exit-

ing through the outer wall. Using this dimension on the Sidewall
Vent Graph below, locate the point intersecting with the slanted
graph line.

2. From the point of this intersection, draw a vertical line to the

bottom of the graph.

3. Select the indicated dimension, and position the fireplace in

accordance with same.

Example: If the vertical dimension from the floor of the
fireplace is 11' (3.4m) the horizontal run to the face of the
outer wall must not exceed 14' (4.3m).

Example: If the vertical dimension from the floor of the unit

is 7’ (2.14m), the horizontal
wall must not exceed
7 ' (2.14m).

run to the face of the outer

Sidewall Vent Graph showing the relationship between vertical and
horizontal dimensions for a Direct Vent flue system.

Figure 10 - Rear Wall Venting Graph

Horizontal Dimension (Ft) From the Outside of

Termination to the Back of the Fireplace

V

ertical Dimension

(

Ft)
From the Floor of Unit to the Center of

the Horizontal V

ent Pipe

Dimensions in Feet

50
48
46
44
42
40
38
36
34
32
30
28
26
24
22
20
18
16
14
12
10
8
6
4
2

2 4 6 8

16

14

12

10

This manual is related to the following products: