BLDV7 Series Gas Fireplace

CLearanCeS

CLearanCeS to CoMBuStIBLeS

ManteL CLearanCeS

note: The combustible area above the facing must not protrude more than 3/4" from the
facing. If it does, it is considered a mantel and must meet the mantel requirements listed in
this manual.

Figure 4 -
Clearances From The Mantel, Ceiling, and Side Wall

w

arn

In

G

Follow these instructions carefully to ensure safe installation. Failure
to follow instructions exactly can create a fire hazard.
the appliance cannot be installed on a carpet, tile or other
combustible material other than wood flooring. If installed on carpet
or vinyl flooring, the appliance shall be installed on a metal, wood
or noncombustible material panel extending full width and depth
of the appliance.

note

All mantel shelves, regardless of depth, should be a minimum of 13" from
top opening of fireplace. Mantel shelf shall not exceed 1" maximum depth
at 13" minimum height from opening.

71” Minimum

Ceiling

13” Min.

From Opening

12” Max.

Depth

6”

Min.

FP2333
BLDV mantel clear

FP333

45°

1”

256O”

3”

5”

156O”

6”

356O”

456O”

FP2334a
BLDV side leg clear

Figure 4a -
Mantel Clearances

Side of Fire-
place Opening

Wall

Combustible
Material Area

FP334a

top View