BLDV7 Series Gas Fireplace

FP2336
flex vent top

VentInG InStaLLatIon InForMatIon

Outside Corner

Inside Corner

Termination Clearances

Termination clearances for buildings with combustible and noncombustible exteriors.

G =

Combustible

6" (152 mm)

Noncombustible

2" (51 mm)

F =

Combustible

6" (152 mm)

Noncombustible

2" (51 mm)

G

Balcony -

with no side wall

M =
Combustible &
Noncombustible
12" (305 mm)

M

Balcony -

with perpendicular side wall

M = 24" (610 mm)
P = 20” (508 mm)

M

F

Alcove Applications*

C

D

C

E

V

V

Combustible &

Noncombustible

V

V

V

E

= Min. 6” (152 mm) for

non-vinyl sidewalls
Min. 12” (305 mm) for
vinyl sidewalls

O

= 8’ (2.4 m) Min.

O

P

584-15

No.

of Caps

D

Min.

C

Max.

1

3’ (914 mm) x D

Actual

6’ (1.8 m)

1 x D

Actual

3

9’ (.7 m)

/3 x D

Actual

4

1’ (3.7 m)

1/ x D

Actual

D

Min.

= # of Termination caps x 3

C

Max.

= ( / # termination caps) x D

Actual

*note: Termination in an alcove space (spaces open only on one side and with an overhang) is permitted with the dimensions specified for vinyl or
non-vinyl siding and soffits. 1. There must be a 3’ (914 mm) minimum between termination caps. . All mechanical air intakes within 10’ (1 m) of a
termination cap must be a minimum of 3’ (914 mm) below the termination cap. 3. All gravity air intakes within 3’ (914 mm) of a termination cap must
be a minimum of 1’ (305 mm) below the termination cap.

GeneraL InForMatIon aSSeMBLInG Vent pIpeS

uSa Installations
The venting system must conform to local codes and/or
the current National Fuel Code ANSI Z3.1/NFPA 54.
Only venting components manufactured by MHSC may
be used in Direct Vent systems.
Canadian Installations
The venting system must be installed in accordance with
the current CSA-B149.1 installation code.

FLex Vent pIpeS

Before joining the flex vent pipe to the unit, apply a bead
of high temperature sealant* (provided) to the 4” pipe
exiting the fireplace. Secure flex vent pipe in place with
a hose clamp (provided).
*Be sure the flex pipe overlaps at least 1” (5 mm) onto
the collars of the fireplace and termination. If the termi-
nation has an internal bead, be sure to overlap and se-
cure 1” (5 mm) past the bead.

* Be sure the vent is actually crushed before proceeding.
Apply a tug to be sure the vent will not slip off the collars.
Repeat process with 7” flex vent pipe. The same proce-
dure must be performed on the vent side.

Apply High Tem-
perature Sealant

Hose Clamp

FP336

Figure 8 -
Apply high temperature
sealant to 4” and 7” pipes

Figure 7 -
Termination Clearances