Mib (management information base), Default parameters, 7 mib (management information base) – MGE UPS Systems 66102 User Manual
Page 9: 8 default parameters

T H E U N I N T E R R U P T I B L E P O W E R P R O V I D E R
Network Management Card – User Manual
34003991EN/GA
- 9 -
Z
Possibility of notification of status changes by e-mail, SMS or SNMP trap
Z
Position detection of 2 dry contacts (maximum sensor/contact distance: 20 m)
Z
Name and status of each configurable contact
Z
Recording of events and measurements in the card log
Z
Possibility of shutting down the installation in the event of a threshold being exceeded or on opening / closure of a dry contact
Z
Connection to the card with straight CAT5 RJ45 network cables (maximum card/sensor distance: 20 m)
Z
Hot installation
1.3.7 MIB (Management Information Base)
Z
Compatible with MIB MGE V1.7
The list of objects managed can be found in the
1.3.8 Default parameters
Function
Parameter
Default value
Possible value
IP address
172.17.16.16
Network IP address
Subnet mask
255.255.0.0
Network IP address
Gateway Address
0.0.0.0
Network IP address
BOOTP/DHCP
Enabled
Active / Deactivated
Firmware Upload
Enabled
Active / Deactivated
SMTP server
smtpserver
31 characters maximum
UPS Contact
Computer Room Manager
49 characters maximum
UPS Location
Computer Room
49 characters maximum
History log interval (sec.)
60
5 to 99999 sec.
Environment log interval (sec.)
300
60 to 99999 sec.
Default Language
English
English / French / Spanish /
German / Italian
empty
50 maximum
User name
MGEUPS
10 characters maximum
Password
MGEUPS
10 characters maximum
Community name read
public
49 characters maximum
Trap port
161
Non configurable
Date and time adjustment
Synchronise with an NTP server
Synchronise with an NTP server
Synchronise manually
NTP server
pool.ntp.org
49 characters maximum
Serial link
Speed
9600 baud
Non configurable
Data bits
8
Non configurable
Stop bits
1
Non configurable
Parity
without
Non configurable
Flow control
without