4.4.4 Central shutdown configuration
Click on "Notified Applications" in the menu, then "Configuration".
This page is used to define either the "shutdown" or the "notification" settings used by the Network Shutdown Modules that connect to
Network Management Card. These settings are used by the Network Shutdown Modules if they are in central-configuration mode or if their
configuration is not valid.
Z
Shutdown duration: the shutdown duration necessary to properly shutdown the computer.
Z
Shutdown after: the time available to the user from the power failure until the launch of the shutoff sequence of the UPS and equipment.
This parameter is optional. Uncheck the box if you wish not to use this parameter.
Z
Broadcast : Sends network notifications to the Administrators and Users groups on events declared in the server hosting the NSM
If you wish to set up a new configuration for the Network Shutdown Modules already set to "central-configuration mode", proceed as indicated
below:
Z
Change the Network Shutdown Module parameters in the "Notified Applications" page.
Z
Click the "Save" button.
Z
In this page, select the NSMs for which you want to apply the new configuration.
Z
Press the "Remove" button.
Z
The NSMs selected will disconnect then reconnect and use the new configuration.