Configuration, Administration, Network – MGE UPS Systems 66102 User Manual
Page 8: List of ports used, Environment sensor, 3 configuration, 4 administration, 5 network, 6 environment sensor, 1 list of ports used

T H E U N I N T E R R U P T I B L E P O W E R P R O V I D E R
Network Management Card – User Manual
34003991EN/GA
- 8 -
Z EMC: 89/336/EEC and 93/68/EEC.
1.3.3 Configuration
The user can configure the card with one of the following means:
Z
Web browser
Z
Local serial link (network parameters)
Z
BOOTP/DHCP (network parameters)
1.3.4 Administration
Z
Up to 50 workstations protected by Network Shutdown Modules - Central or local configuration.
Z
Up to 5 browsers connected at the same time (3 in SSL).
Z
Minimum recommended browser versions: Internet Explorer 6.x, Mozilla Firefox 1.5, Netscape 6.x
Z
E-mail sending configurable according to UPS alarms and transmission of a periodical report.
Z
Control of UPS on/off switching via the HTML interface.
Z
Adjustment and control of PowerShare outlets via the HTML interface, sequential starting of the installation and optimisation of backup
time by shutting down non-priority systems.
Z
Automatic data and time adjustment via NTP server.
Z
Protection by encrypted password.
Z
Protection by secure SSL connection.
Z
Saving of logs in the non-volatile memory.
Z
Languages available: English / French / Spanish / German / Italian
Z
On-line help in English available for each page.
Z
Card firmware updated via the network
1.3.5 Network
Z
Fast ETHERNET 10/100 Mbits compatibility with auto-negotiation on the RJ45 outlet
1.3.5.1 List of ports used
Z
BootP, DHCP
UDP 68 , 67
Z
HTML
TCP 80
Z
SSL
TCP 443
Z
NSM connection
TCP 5000
Z
SMTP 25
Z
NTP
123
Z
SNMP V1
161
Z
TRAP SNMP
162
1.3.6 Environment sensor
Z
Temperature measurement from 0 to 70°C with +/- 1°C accuracy
Z
Measurement of humidity from 0 to 100% with +/- 6% accuracy
Z
Min / max time-stamped function for temperature and humidity
Z
Choice of temperature readings in Celsius or Fahrenheit
Z
High and low thresholds, hysteresis and offset adjustable via Web interface