CFX Vent Free Fireplace System

20301726

Note: All troubleshooting items are listed in order
of operation.

TROUBLESHOOTING

OBSERVED PROBLEM POSSIBLE CAUSE

REMEDY

When ignitor button is
pressed, there is no spark
at ODS/pilot.

1. Ignitor electrode positioned wrong.

1 Replace ignitor.

2. Ignitor electrode is broken.

2. Replace ignitor.

3. Ignitor electrode not connected to ignitor

cable.

3. Reconnect ignitor cable.

4. Ignitor cable pinched or wet. Keep ignitor

cable dry.

4. Free ignitor cable if pinched by any metal

or tubing.

5. Broken ignitor cable.

5. Replace ignitor cable.

6. Bad piezo ignitor.

6. Replace piezo ignitor.

Appliance produces
unwanted odors.

1. Appliance burning vapors from paint, hair

spray, glues, etc.

1. Ventilate room. Stop using odor causing

products while heater is running.

2. Gas leak.

2. Locate and correct all leaks.

3. Initial burn off

3. Ventilate room and turn unit on high until

odor is gone. Odor should be gone after 2
to 3 hours of continuous use.

Appliance shuts off during
use.

1. Not enough fresh air is available for

ODS/ pilot to operate.

1. Open window and/or door for ventilation.

2. Low line pressure.

2. Contact local gas company.

3. ODS/pilot is partially clogged.

3. Clean ODS/pilot.

4. Defective Thermopile.

4. Check wire connections. Check output

should be 500 milli-volts across TH/TP
and TP Terminals with ON/OFF switches
off.

5. Restrictions in incoming air flow.

5. Check for bottom riser on glass door,

sunken fireplace, excessive lava rock/
cinders densely packed against grate.

Gas odor even when
control knob is in OFF
position.

1. Gas leak.

1. Locate and correct all leaks.

2. Control valve defective.

2. Replace control valve.

When ignitor button is
pressed, there is spark at
ODS pilot, but no ignition.

1. Gas supply turned off or manual shutoff

valve closed.

1. Turn on gas supply or open manual shutoff

valve.

2. Control knob not in PILOT position.

2. Turn control knob to PILOT position.

3. Control knob not pressed in while in

PILOT position.

3. Press in control knob while in PILOT

position.

4. Air in gas lines when installed.

4. Continue holding down control knob.

Repeat igniting operation until air is
removed.

5. ODS/pilot is clogged.

5. Replace ODS/pilot assembly or get it

serviced.

6. Gas regulator setting is not correct.

6. Check incoming pressure. Replace gas

regulator.

W

ARNING

Turn appliance OFF and allow to cool before
servicing. Only a qualified service person
should service and repair the heater.