beautypg.com

Installation and user manual – MGE UPS Systems STS 600A User Manual

Page 53

background image

Installation and User Manual

Operation

3 —15

86-504004-00 B03

3.15

Epsilon STS™ Customization

Certain parameters can be customized as follows:

1.

Press the

button.

2.

Select , then using the function buttons marked

or

.

3.

Confirm by pressing the function button marked

4.

Enter the password (default factory password is “0 0 0”. Select Setup, then Password to change the
password).

Figure 3-6: Customization Screen.

Table 3-1: Customization Settings.

Parameter

Factory setting

Customization

Nominal Voltage (both sources)

As specified by customer

208,220,240,440,480,575,600V

Overvoltage threshold

+10%

+5% to +20% (1% steps)

Undervoltage threshold

-10%

-5% to –20% (1% steps)

Nominal Frequency (both sources)

60 Hz

50 or 60 Hz

Over-frequency threshold

+5%

+1 to +10% (0.5% steps)

Under-frequency threshold

-5%

-1 to -10% (0.5% steps)

Phase error tolerance (between sources)

±15°

±1° to ±45° (1° steps)

Retransfer Automatic

(YES)

Manual

(NO)

(return to preferred source after transfer)

For additional customization of your Epsilon STS™ (e.g. to change the retransfer time delay from the factory setting
of 10 seconds), we recommend that you contact our MGE Customer Support (reference page QS-8).

Customization active

Nominal Voltage

480V

Overvoltage threshold

10%

Undervoltage threshold

10%

Nominal frequency

60 Hz

Over-frequency threshold

5%

Under-frequency threshold

5%

Phase error tolerance S1/S2

15°

Retransfer

YES

E

S

C

This manual is related to the following products: