Epilson sts – MGE UPS Systems STS 600A User Manual
Page 24
1.7
System Specifications
Recommended environment
20° to 25°C (68° to 77°F); 50% relative humidity; computer room or other
temperature and humidity-controlled environment.
Operating temperature
10° to 40°C (50° to 104°F).
Storage
-10° to 60°C (-14° to 140°F).
Humidity
up to 95% non-condensing (operating).
Altitude
sea level to 8,500 feet without derating.
Acoustic noise
65 dBA typical at rated load as measured 5 feet from the front of the STS module.
1.7.1
Electrical Electrical Characteristics
Nominal Input Voltage
208, 220, 240, 440, 480, 575, 600 VAC ± 15%, three(3) phase, 3 or 4-wire plus
ground.
Nominal Output
208, 220, 240, 440, 480, 575,600 VAC ± 15%, three(3) phase, 3 or 4-wire plus
Voltage
ground to correspond with input voltage. .
Maximum Continuous
200, 400, 600 Amps.
Current
Molded Case Switch
250, 400, 600 Amps.
Rating
Input/Output
50/60 Hz ± 5 Hz.
Frequency
Load Power Factor
Unity to 0.60 lagging or
leading.
Non-Linear Loads
100% of its rating up to
Capability
maximum crest factor of 3.5.
Overload Rating
150% for 15 minutes;
1000% for three(3) cycles.
Source Voltage
Up to 10% THD with notching
Distortion
and ringing transients.
Output Voltage
Less than 1% added.
Distortion
Voltage Transient
Up to 6 KV (6000 volt spike) per IEEE C62.41 for Cat. B3. Meets EN 50082-1
Withstand
(with optional TVSS installed). Such transient levels shall not effect the
operation of the STS. The STS may transfer on over-voltage conditions.
Short Circuit Withstand
Up to 100KA.
Harmonic Current
Unlimited.
(Feedback from the
Load)
Emission Limits
Meets FCC Part 15 Class A, EN 50081-2.
Epilson STS
TM
Introduction
1 — 8
86-504004-00 B03