beautypg.com

Epilson sts – MGE UPS Systems STS 600A User Manual

Page 50

background image

Figure 3-3: Manual Operation Pushbuttons.

Epilson STS

TM

Operation

3 —12

86-504004-00 B03

Manual Control keyed switch- The "Return to Preferred Source", "Change

Preferred Source" and "Override Limits"

manual control pushbuttons are active

(enabled) in the "ON" position,

and inactive (disabled) in the "OFF"

position.

Override Limits pushbutton

- enables manual transfers in out-of-phase conditions

when depressed simultaneously with the CHANGE

PREFERRED

SOURCE

pushbutton.

- requires MANUAL CONTROL switch to be in

the ON position.

Change Preferred Source pushbutton

- selects other source as preferred, causing

a transfer to the selected source if it is not

the active source.

- requires MANUAL CONTROL switch to be

in the ON position.

Lamp Test pushbutton

- turns on all LEDs on the front panel

- sounds the audible alarm horn

Alarm Silence pushbutton

- always active

- silences audible alarm horn

Return to Preferred Source pushbutton

- temporarily enables auto-retransfer when

retransfer function is switched off (re-transfer

disabled) and initiates a retransfer back to the

preferred source, overriding the owner selected

auto retransfer time delay. Auto-retransfer will

again be disabled after the re-transfer is

completed.

- requires MANUAL CONTROL switch to be

in the ON position.

ALARM
SILENCE

LAMP
TEST

RETURN TO
PREFERRED
SOURCE

CHANGE
PREFERRED
SOURCE

OVERRIDE
LIMITS

ON

OFF

MANUAL

CONTROL

This manual is related to the following products: