beautypg.com

Installation and user manual – MGE UPS Systems STS 600A User Manual

Page 27

background image

Installation and User Manual

Figure 1-6: 400/600 STS Power and Control Wire Connections.

Table 1-2: Input/Output Power Connections.

STS

# OF CABLES PER

MINIMUM

CABLE LUG

CONDUIT

RATING PHASE

N GND

CABLE SIZE

(SUPPLIED)

HOLE

(AMPS)

(75°C, CU)

DIA. (QTY.)

400

2

4

1

# 250 MCM

# 250 MCM, 3/8” STUD 4” (3)

(T&B M973 OR EQUIV.)

600

3

5

1

# 250 MCM

# 250 MCM, 3/8” STUD

4-1/2” (3)

(T&B M973 OR EQUIV.)

Introduction

1 — 11

86-504004-00 B03

CONTROL WIRES
THREADED THROUGH
UNIT.

CONTROL WIRE

PANDUIT/WIRE-WAYS

TOP ENTRY
CONDUIT PLATE

BRACE AT
12" INTERVALS

BOTTOM ENTRY
CONDUIT PAN

COMMUNICATION

CARDS

TB1

TERMINAL

CONTROL WIRES

CONTROL WIRE

PANDUIT/WIRE-WAYS

This manual is related to the following products: