Installation and user manual – MGE UPS Systems STS 600A User Manual
Page 27
Installation and User Manual
Figure 1-6: 400/600 STS Power and Control Wire Connections.
Table 1-2: Input/Output Power Connections.
STS
# OF CABLES PER
MINIMUM
CABLE LUG
CONDUIT
RATING PHASE
N GND
CABLE SIZE
(SUPPLIED)
HOLE
(AMPS)
(75°C, CU)
DIA. (QTY.)
400
2
4
1
# 250 MCM
# 250 MCM, 3/8” STUD 4” (3)
(T&B M973 OR EQUIV.)
600
3
5
1
# 250 MCM
# 250 MCM, 3/8” STUD
4-1/2” (3)
(T&B M973 OR EQUIV.)
Introduction
1 — 11
86-504004-00 B03
CONTROL WIRES
THREADED THROUGH
UNIT.
CONTROL WIRE
PANDUIT/WIRE-WAYS
TOP ENTRY
CONDUIT PLATE
BRACE AT
12" INTERVALS
BOTTOM ENTRY
CONDUIT PAN
COMMUNICATION
CARDS
TB1
TERMINAL
CONTROL WIRES
CONTROL WIRE
PANDUIT/WIRE-WAYS