VENT INSTALLATION

Figure 7 - Combustible Clearances for Vent Pipe

A minimum of 3" clearance to the top is

required along horizontal length until fl ue

pipe penetrates outside wall.

A minimum 1"

clearance to

combustibles

permitted all

around fl ue at

outside wall

Horizontal sections of this vent system require a minimum
of 3" clearances to combustibles at the top of the fl ue
and 1" clearance at the sides and bottom until the fl ue
penetrates the outside wall.
A minimum 1" clearance all
around the fl ue is acceptable at this point of penetration.

Vertical sections of this vent system require a minimum of
1" clearance to combustibles on all sides of the pipe.

W

ARNING

12" vertical rise required

before horizontal run