PRE-INSTALLATION CHECKS

1. VENTILATION

1.1 This appliance requires ventilation to supply combustion air.

Any room containing the appliance must have a permanent

air vent opening with a total free area of at least 550mm

2

per kW of appliance rated output above 5kW.

1.2 Increase air supply provisions where a room contains

multiple appliances.

1.3 If vents open into adjoining rooms or spaces there must be

an air vent of at least the same size direct to the outside.

1.4 Permanent air vents should be non-adjustable and

positioned where they are unlikely to become blocked.

1.5 Site the vents where cold draught is unlikely to cause

discomfort. This can be avoided by placing vents near

ceilings or close to the appliance, see Diagram opposite.

Without liner system (round) mm

150

150

150

150

150

minimum dimension (dia.) inch

6

6

6

6

6

Flue/Chimney Size

Without liner system (square) mm

135

135

135

135

135

minimum dimension inch

5

1

/

2

5

1

/

2

5

1

/

2

5

1

/

2

5

1

/

2

Liner or factory made system (dia.) mm

150

150

150

150

150

installed in accordance with manufacturers instructions

inch

6

6

6

6

6

Riva

40

Riva

55

Riva

66

Riva

66

Avanti

* When measured from the top of the stove to the top of the flue, with no horizontal sections

and a maximum of 4 bends with angles of less than 45°

May be 125mm (5”) if only burning low volatiles (smokeless) fuels approved for use in Smoke Contol Areas.

See web site http://uksmokecontrolareas.co.uk for more information about approved fuels.

Model
Riva 40-RV 40/RV40B
Riva 55-RV 55/RV55B
Riva 66-RV 66/RV66B
Riva 66 Avanti-RV66 AVC
Riva 66-RV76/RV76B

Riva

76

Flue/Chimney All Products

m

4.5

4.5

4.5

4.5

4.5

minimum height*

feet

13

13

13

13

13

Do not connect to systems containing large voids or over 9" (230mm) square/round