Expanded heating data, Xpanded, Eating – Goodman Mfg CPH COMMERCIAL SS-CPH90-150 User Manual
Page 7: Roduct, Pecifications
6
www.goodmanmfg.com
SS-CPH90-150
SS-CPH90-150
www.goodmanmfg.com
7
P
roduct
S
PecificationS
P
roduct
S
PecificationS
e
xPaNded
H
eatiNg
d
ata
CPH090
Outdoor Ambient Temperature
65
60
55
50
47
45
40
35
30
25
20
17
15
10
5
0
-5
-10
MBh
114.4 108.3 101.9
95.3
91.0
88.2
81.9
75.5
70.5
65.0
59.9
56.6
54.5
48.9
43.3
37.8
32.2
26.4
T/R
35.3
33.4
31.5
29.4
28.1
27.2
25.3
23.3
21.7
20.1
18.5
17.5
16.8
15.1
13.4
11.7
9.9
8.2
kW
8.22
8.06
7.91
7.75
7.66
7.59
7.44
7.29
6.93
6.78
6.63
6.54
6.49
6.33
6.19
6.04
5.89
5.74
Amps
30.2
28.4
26.9
25.6
24.9
24.5
23.4
22.5
21.8
21.1
20.3
20.0
19.8
19.1
18.2
17.4
16.5
15.4
COP
4.07
3.93
3.77
3.60
3.48
3.40
3.22
3.03
2.98
2.81
2.64
2.53
2.46
2.26
2.05
1.83
1.60
1.35
HI PR
424
406
390
373
365
358
344
330
316
302
290
283
278
267
257
246
238
229
LO PR
134
124
117
107
101
97
89
80
72
64
56
52
51
43
37
31
27
21
CPH102
Outdoor Ambient Temperature
65
60
55
50
47
45
40
35
30
25
20
17
15
10
5
0
-5
-10
MBh
128.2 121.4 114.2 106.8 102.0
98.8
91.8
84.7
69.2
63.8
58.8
55.5
53.4
48.0
42.5
37.1
31.6
25.9
T/R
34.9
33.1
31.1
29.1
27.8
26.9
25.0
23.1
18.8
17.4
16.0
15.1
14.6
13.1
11.6
10.1
8.6
7.1
kW
9.34
9.17
8.99
8.82
8.72
8.64
8.48
8.30
7.8
7.7
7.5
7.4
7.3
7.2
7.0
6.9
6.7
6.5
Amps
37.6
35.2
33.2
31.6
30.6
30.1
28.7
27.5
26.6
25.6
24.6
24.2
23.9
23.0
21.8
20.8
19.6
18.2
COP
4.02
3.87
3.72
3.54
3.42
3.35
3.17
2.98
2.6
2.4
2.3
2.2
2.1
2.0
1.8
1.6
1.4
1.2
HI PR
13.7
13.2
12.7
12.1
11.7
11.4
10.8
10.2
8.8
8.3
7.8
7.5
7.3
6.7
6.1
5.4
4.7
4.0
LO PR
419
401
386
369
360
354
340
326
312.5 298.4 286.5 279.7 274.6 264.2 254.1 243.6 235.0 226.7
LO PR
136
126
118
108
103
99
91
81
73
65
57
53
51
43
37
32
28
22
CPH120
Outdoor Ambient Temperature
65
60
55
50
47
45
40
35
30
25
20
17
15
10
5
0
-5
-10
MBh
150.8 142.8 134.4 125.6 120.0 116.3 108.0
99.6
87.7
81.0
74.6
70.4
67.8
60.8
53.9
47.0
40.1
32.9
T/R
34.9
33.1
31.1
29.1
27.8
26.9
25.0
23.1
20.3
18.7
17.3
16.3
15.7
14.1
12.5
10.9
9.3
7.6
kW
10.70 10.50 10.31 10.11 10.00
9.92
9.73
9.54
8.65
8.47
8.30
8.20
8.13
7.95
7.78
7.61
7.44
7.27
Amps
41.3
38.9
36.9
35.3
34.3
33.8
32.4
31.2
30.2
29.3
28.3
27.8
27.6
26.6
25.4
24.4
23.3
21.8
COP
4.13
3.98
3.82
3.64
3.51
3.43
3.25
3.06
2.97
2.80
2.63
2.51
2.44
2.24
2.03
1.81
1.58
1.32
HI PR
439
421
405
387
378
371
356
342
328
313
301
293
288
277
266
256
246
238
LO PR
133
123
115
106
100
96
89
79
71
64
56
52
50
42
37
31
27
21
Above information is for nominal CFM and 70 degree indoor dry bulb. Instantaneous capacity listed.
Amps = unit amps (comp.+fans)
High pressure measured at liquid line access fitting; Low pressure measured at compressor suction access fitting.
kW = Total system power
CPH150
Outdoor Ambient Temperature
65
60
55
50
47
45
40
35
30
25
20
17
15
10
5
0
-5
-10
MBh
178.5 169.0 159.0 148.7 142.0 137.6 127.8 117.9 104.7
96.6
89.0
84.0
80.9
72.6
64.3
56.1
47.9
39.2
T/R
39.4
37.3
35.1
32.8
31.3
30.3
28.2
26.0
23.1
21.3
19.6
18.5
17.8
16.0
14.2
12.4
10.6
8.6
kW
13.89 13.64 13.39 13.14 13.00 12.89 12.65 12.40 12.36 12.10 11.85 11.70 11.60 11.34 11.09 10.85 10.59 10.34
Amps
3.76
3.62
3.48
3.31
3.20
3.12
2.96
2.78
2.48
2.34
2.20
2.10
2.04
1.87
1.70
1.51
1.32
1.11
COP
12.8
12.4
11.9
11.3
10.9
10.7
10.1
9.5
8.5
8.0
7.5
7.2
7.0
6.4
5.8
5.2
4.5
3.8
HI PR
471
452
434
415
405
398
382
367
351
336
322
315
309
297
286
274
264
255
LO PR
129
120
113
103
98
94
86
77
69
62
54
51
49
41
36
30
26
21
Design Super Heat 7°± 2 @ Suction Service Port 47 test condition