Product specs — 12½ tons, 12½ t, Roduct – Goodman Mfg CPH COMMERCIAL SS-CPH90-150 User Manual
Page 6: Pecifications
6
www.goodmanmfg.com
SS-CPH90-150
SS-CPH90-150
www.goodmanmfg.com
7
P
roduct
S
PecificationS
P
roduct
S
PecificationS
P
roduct
S
PecificationS
— 12½ t
onS
CPH150
***3B***A*
CPH150
***4B***A*
CPH150
***7B***A*
Cooling Capacity
Total, BTU/h
140,000
140,000
140,000
Sensible BTU/h
98,000
98,000
98,000
EER / IEER
10.6 / 10.7
10.6 / 10.7
10.6 / 10.7
Decibels
83
83
83
ARI Reference #s
5104784
5104784
5104784
Heating Capacity
BTU/hr (47°F)
142,000
142,000
142,000
COP (47°F)
3.2
3.2
3.2
BTU/hr (17°F)
82,000
82,000
82,000
COP (17°F)
2.1
2.1
2.1
Evapoartor Motor / Coil
Motor Type (Belt Drive)
AX49
AX49
AX49
Indoor Nominal CFM
5,000
5,000
5,000
Indoor Motor FLA (Cooling)
9.4
4.7
4.2
Horsepower - RPM
3.0 - 1,725
3.0 - 1,725
3.0 - 1,725
Piston Size (Cooling)
0.096
0.096
0.096
Filter Size (Qty)
(4) 20" x 25" x 2"
(4) 20" x 25" x 2"
(4) 20" x 25" x 2"
Drain Size (NPT)
¾"
¾"
¾"
R-410A Refrigerant Charge Cir #1 & #2 (oz.)
290 / 290
290 / 290
290 / 290
Evaporator Coil Face Area (ft²)
14.7
14.7
14.7
Rows Deep / Fins per Inch
4 / 15
4 / 15
4 / 15
# of Wheels (D x W)
(1) 15" x 15"
(1) 15" x 15"
(1) 15" x 15"
Motor Sheave / Blower Sheave
VL40 / AK66
VL40 / AK66
VL40 / AK66
Condenser Fan / Coil
Quantity of condenser Fan Motors
2
2
2
Horsepower - RPM
⅓ - 1,075
⅓ - 1,075
⅓ - 1,075
Fan Diameter / # Fan Blades
22/ 3
22/ 3
22/ 3
Outdoor Nominal CFM
7,200
7,200
7,200
Face Area (ft²)
35.3
35.3
35.3
Rows Deep / Fins per Inch
2/3 rows 15 fpi
2/3 rows 15 fpi
2/3 rows 15 fpi
Piston Size (Heating)
0.067
0.067
0.067
Compressor
Quantity / Stage
2 / Single
2 / Single
2 / Single
Type
Scroll
Scroll
Scroll
Compressor RLA / LRA ea.
22.4 / 149
10.6 / 75
7.7 / 54
Electrical Data / Static
Voltage / Phase / Frequency
208-230/ 3/ 60
460/ 3/ 60
575/ 3/ 60
Standard Max Static
1.4"
1.4"
1.4"
Outdoor Fan FLA ea.
2.4
1.2
0.9
Total Unit Amps
59
28
21.4
Min. Circuit Ampacity¹
65
31
23
Max. Overcurrent Protection (amps)²
80
40
30
Entrance Power Supply & Control Voltage
Locating Dimple
Locating Dimple
Locating Dimple
Operating Weight (lbs)
1325
1325
1325
Ship Weight (lbs)
1350
1350
1350
¹ Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.
² May use fuses or HACR-type circuit breakers of the same size as noted.
Notes
• Always check the S&R plate for electrical data on the unit being installed.
• When a factory-installed powered convenience outlet is installed in the equipment, the unit MCA (Min. Circuit Ampacity) will increase by 7.5A for
208/230V units, increase by 3.75A for 460V units, and by 3A for 575V units. The MOP (Max. Overcurrent Protection) device must be sized accordingly.