2

www.goodmanmfg.com

SS-CPH90-150

SS-CPH90-150

www.goodmanmfg.com

3

P

roduct

S

PecificationS

P

roduct

S

PecificationS

P

roduct

S

PecificationS

— 7½ t

onS

CPH090

***3B***A*

CPH090

***4B***A*

CPH090

***7B***A*

Cooling Capacity
Total BTU/h

90,000

90,000

90,000

Sensible BTU/h

65,700

65,700

65,700

EER / IEER

11.5 / 11.5

11.5 / 11.5

11.5 / 11.5

Decibels

83

83

83

AHRI Reference #s

5104781

5104781

5104781

Heating Capacity
BTU/h / COP (47° F)

90,000 / 3.4

90,000 / 3.4

90,000 / 3.4

BTU/h / COP (17° F)

55,000 / 2.4

55,000 / 2.4

55,000 / 2.4

Evaporator Motor / Coil
Motor Type

Belt Drive

Belt Drive

Belt Drive

Indoor Nominal CFM

3,000

3,000

3,000

Indoor Motor FLA (Cooling)

7.8

3.9

2.5

Horsepower - RPM

2.0 - 1725

2.0 - 1725

2.0 - 1725

Piston Size (Cooling)

0.076

0.076

0.076

Filter Size

16" x 24" x 2"

16" x 24" x 2"

16" x 24" x 2"

Drain Size (NPT)

¾"

¾"

¾"

R-410A Refrigerant Charge: Cir #1 / #2 (oz.)

215 / 215

215 / 215

200 / 200

Evaporator Coil Face Area (ft²)

10.2

10.2

10.2

Rows Deep / Fins per Inch

4 / 16

4 / 16

4 / 16

Belt Drive Evap Fan Data
# of Wheels (D x W)

1 (15" x 12")

1 (15" x 12")

1 (15" x 12")

Motor Sheave / Blower Sheave

VL40 / AK74

VL40 / AK74

VL40 / AK74

Belt

AX51

AX51

AX51

Condenser Fan / Coil
Quantity of Condenser Fan Motors

2

2

2

Horsepower - RPM

¼ - 1090

¼ - 890

¼ - 1075

Fan Diameter / # Fan Blades

22 / 4

22 / 4

22 / 4

Outdoor Expansion Device

0.052

0.052

0.055

Outdoor Nominal CFM

7,600

7,600

7,600

Face Area (ft²)

32.4

32.4

32.4

# Coils / Rows Deep - Fins per Inch

2 / 2 - 20

2 / 2 - 20

2 / 2 - 20

Piston Size (Heating)

0.052

0.052

0.055

Compressor
Quantity / Type / Stage

2 / Scroll / 1

2 / Scroll / 1

2 / Scroll / 1

Compressor RLA / LRA

13.1 / 83.1

6.1 / 41.0

4.4 / 33.0

Electrical Data
Voltage / Phase / Frequency

208-230 / 3 / 60

460 / 3 / 60

575 / 3 / 60

Indoor Blower HP / FLA

1.5 / 5.0

1.5 / 2.5

2 / 2.5

Outdoor Fan HP / FLA

¼ / 1.4

¼ / 0.8

¼ / 0.6

Total Unit Amps

36.9

17.7

12.5

Min. Circuit Ampacity¹

40

19

13.6

Max. Overcurrent Protection (amps)²

50

25

15

Entrance Power Supply & Control Voltage

Locating Dimple

Locating Dimple

Locating Dimple

Operating Weight (lbs)

1135

1135

1135

Ship Weight (lbs)

1175

1175

1175

¹ Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.

² May use fuses or HACR-type circuit breakers of the same size as noted.

Notes

• Always check the S&R plate for electrical data on the unit being installed.

• When a factory-installed powered convenience outlet is installed in the equipment, the unit MCA (Min. Circuit Ampacity) will increase by 7.5A for

208/230V units, increase by 3.75A for 460V units, and by 3A for 575V units. The MOP (Max. Overcurrent Protection) device must be sized accordingly.