beautypg.com

Kitchen hoods • type i and type ii – Greenheck Fan Canopy Type Kitchen Hoods 452413 User Manual

Page 23

background image

23

Kitchen Hoods • Type I and Type II

HOOD-1B

HOOD-1A

FROM MAKE-UP AIR

STARTER #3

TO EXHAUST FAN

DISCONNECT SWITCH

WIRED THROUGH

BREATHER TUBE ONLY

FROM MAKE-UP AIR

STARTER #2

TO EXHAUST FAN

DISCONNECT SWITCH

WIRED THROUGH

BREATHER TUBE ONLY

EXHAUST FAN-1A

EXHAUST FAN-1B

POWER

PANEL

SUPPLY POWER TO

JUNCTION BOX

ON HOOD FOR HOOD LIGHTS

JUNCTION BOX ON
TOP OF HOOD FOR
FIELD CONNECTION
OF SUPPLY POWER

FIVE (5) CONTROL WIRES
FROM SWITCH JUNCTION
BOX ON HOOD TO MAKE-UP
AIR CONTROL CENTER

CONTROL CENTER

MAKE-UP AIR UNIT

FIELD WIRING

SUPPL

Y POWER

TO MAKE-UP AIR

CONTROL CENTER

TWO (2) CONTROL WIRES FROM
ANSUL SNAP ACTION SWITCH TO
MOTOR CONTROLS AREA.
ELECTRICAL CONTRACTOR TO
PROVIDE HANDIBOX ON SIDE
OF AUTOMAN.
ANSUL AUTOMAN IS NOT AN
ELECTRICAL RATED BOX.
NO CONNECTIONS INSIDE.

Optional

Disconnect

Switch

(field installed)

Disconnect

Switch in

Control Center

Kitchen

Fan

Control

Center

Fire System
Control Box

24 VCD make-up air controls

To appliance shunt trip breaker

To electrial gas valve

To building alarm

To mechanial gas valve

These components may be
mounted in a hood-mounted end
cabinet or on a wall near the hood.

NOTE: Make-up air
fan will have starters
in make-up air only.
Control wiring must
be run to KFCC.

TYPICAL

EXHAUST

FAN

TO REMOTE CIRCUIT BREAKERS

______V ____Ph ____ Amp for make-up air fan

120 V 1 Ph 15 Amp for controls

120 V 1 Ph 15 Amp for hood lights

______V ____Ph ____ Amp for exhaust fan

______V ____Ph ____ Amp for supply fan

TYPICAL

HOOD

TYPICAL

SUPPLY FAN

FIELD WIRING

TYPICAL

MAKE-UP AIR FAN

NC

NO

NC

NO

This arrangement requires individual power connections for each supply and exhaust fan from remote circuit breakers
thru the fans starter in the Kitchen Fan Control Center (KFCC). The make-up air fan will be wired directly from a remote
breaker. It requires control wiring to be run to the KFCC.

Light and Fan Switch Locations:
A. KFCC

D. UDS

B. Utility Cabinet

E. Hood

C. Wall

F. WWCP

TERMINAL STRIP

IN KFCC

HOOD LIGHTS

(1400 WATT MAX.)

M2

M1

M1

10

12

S1

120/1

15 AMP

11

9

8

7

Overall Wiring Plan View for Kitchen Systems with Make-Up Air Control Centers