beautypg.com

Greenheck Fan Steel Airfoil Blades FSD-311V User Manual

Fire smoke dampers, Model fsd-311v combination, Application

background image

APPLICATION

Model FSD-311V is a vertical blade class I leakage rated combi-

nation fire smoke damper. High strength airfoil blades ensure the

lowest resistance to airflow in HVAC systems with velocities to 4000

fpm (20.3m/s) and 4 in. wg (1.0 kPa).

RATINgs

UL 555 Fire Resistance Rating:

Fire Rating:

1½ hours

Dynamic Closure Rating: Actual ratings are size dependent

Max. Velocity:

up to 4000 fpm (20.3 m/s)

Max. Pressure:

4 in. wg (1 kPa)

UL555S Leakage Rating:

Leakage Class:

I

Operational Rating:

Actual ratings are size dependent

Max. Velocity:

up to 4000 fpm (20.3m/s)

Max. Pressure:

4 in. wg (1 kPa)

Maximum Temperature: 350°F (177°C)- depending upon

the actuator

sTANdARd CONsTRuCTION

Frame:

5 in. x 1 in. (127mm x 25mm)

galvanized steel hat channel with

reinforced corners. A low profile

head and sill are used on sizes less

than 17 in. (432mm) high to

maximize free area and

performance.

Blades:

Double skin airfoil shape of

galvanized steel with full length

structural reinforcement. 14 ga.

(2 mm) equivalent thickness.

seals:

Extruded silicone rubber blade

seals. Flexible stainless steel jamb

seals.

Closure device:

RRL 165°F (74°C)

Linkage:

Concealed in jamb.

Axles:

1

/

2

in. (13mm) dia. plated steel.

Bearings:

304 stainless steel

sIze LImITATIONs:

minimum size:

6 in. W x 8 in. H

(152mm W x 203mm H)

maximum size-

Single Section:

50 in. W x 32 in. H

(1270mm W x 813mm H)

Multiple Section:

100 in. W x 32 in. H

(2540mm W x 813mm H)

OPTIONAL FeATuRes

• OCI (Open closed indication switches)

• Electric or pneumatic actuators to accomplish smoke

management and system functions.

• Transitions (R, C, O)

• POC retaining angles

• Momentary Switch

• Sealed transitions and sleeves

• RRL/OCI (Open closed indication switches)

• 165ºF (74°C), 212ºF (100°C), 250ºF (121°C), 350ºF (177°C) RRL's

available

• TOR (remote override closure allows damper to perform smoke

management functions during a fire emergency.)

• PRV (pneumatic relief valve)

• Security Bars

• Sealed transitions and sleeves

model Fsd-311V

Combination

FIRe smOKe dAmPeRs

Steel Airfoil Blades

UL 555S Leakage Class I

UL555 1 1/2 Hour Fire Resistance Rating

*W&H dimensions furnished approximately

1

/

4

in. (6mm) undersize.

W*

H*

Model FSD-311V meets the requirements for fire

dampers, smoke dampers and combination fire

smoke dampers established by:

National Fire Protection Association

NFPA Standards 80, 90A, 92A, 92B, 101 & 105

IBC International Building Codes

ICBO uniform Building Codes

CsFm California state Fire marshal
Fire Damper Listing (#3225-0981:103)
Leakage (Smoke) Damper Listing (#3230-0981:104)

New York City (MEA listing #260-91-M)

“uL CLAssIFIed (see complete marking on

product)”

“uL CLAssIFIed to Canadian safety standards

(see complete marking on product)”

Standard 555 & 555S (Listing #R13317)

Installation instructions available at www.greenheck.com