beautypg.com

Performance curve – Grizzly G0442 User Manual

Page 39

background image

Model g0442/g0601 (Mfg since 3/12)

-37-

figure 56. Additional factors affecting static

pressure.

additional factors

static pressure

seasoned (well used)

dust Collection Filter

1"

entry Loss at Large

Machine hood

2"

figure 57. totaling static pressure numbers.

Main Line

6" Rigid Pipe (0.037) at 20'

................ 0.740

Branch Line

4" Rigid Pipe (0.075) at 10'

................ 0.750

4" Flex Pipe (0.28) at 5' ........................ 1.400

Elbows/Branches

6" 45˚ Y-Branch

................................ 0.329

4" 45˚ Elbow ........................................ 0.225

Additional Factors

Seasoned Filter

................................ 1.000

Total Static Pressure Loss ................ 4.444

4. total your list as shown in the example below

to come up with your overall static pressure
loss number for that line.

note: Always account for a seasoned filter,
so you don't end up with a system that only
works right when the filter is clean.

note: When calculating static pressure loss
to determine if multiple lines can be left open
at the same time, only include the main line
numbers once.

3. Add the additional factors from the following-

table to your list.

5. Compare the total static pressure loss for that

line to the closest CFM given in

figure 58.

example: the g0442/g0601 data sheet

performance curve is illustrated in figure

58. Find 4.6 on the static pressure axis (the
amount of total static pressure loss calcu-
lated in

figure 57), then refer to the closest

value on the CFM axis—approximately 1953
CFM.

the 1953 CFM for the static pressure loss of
the line connected to the router is well above
the 220 CFM requirement of that machine.

— if the CFM for your static pressure loss

is above the requirement of the machine
connected to the end of that branch line,
then dust collection will most likely be
successful. Congratulations! you've just
designed your own dust system. refer to
the

accessories section on page 42 to

start buying the components necessary to
make your system a reality.

figure 58. g0442/g0601 performance curve

chart and data.

performance curve

2500
2250
2000
1750
1500
1250
1000

750
500
250

0

0.0

1.0

2.0

3.0

4.0

5.0

6.0

7.0

8.0

9.0

10.0 11.0 12.0 13.0

2184

cfm

static pressure (inch/h2o)

5 hp grizzly dust collector performance results
max cfm max sp hp

volts

inlet

impeller

2184

14.0

5 hp

220v

10"

16"

restrictor plate
(inch)

dia
10"

dia
9"

dia.
8"

dia.
7"

dia.
6"

dia.
5"

dia.
4"

dia.
3"

dia.
2"

static pressure
(inch/h2o)

1.9

2.1

3.0

4.6

7.0

9.8

12.1 13.2 13.7

CFM

2184 2129 2072 1953 1692 1381 977 691 488

the airflow test probe is located 1.5x duct diameter upstream from
the air inlet. test pipe length is a minimum of 10x duct diameter.