INSTAllATION INSTRUCTIONS

SITE REQUIREMENTS

1. FlUE AND ChIMNEY REQUIREMENTS

1.1 The chimney or flue system must comply with the rules in

force, and must be a minimum of 125mm (5”) in diameter.

Pre cast flues must conform to BS1289: 1986. The cross

sectional area of the flue must be 16500 mm

2

with a

minimum dimension of 90mm.

*When fitting the appliance to a pre cast flue, the total

minimum depth of fire opening necessary is (D) 215mm. This

allows a 25mm space behind the appliance for debris,

required on this type of flue system. This is achieved either by

using = (A) a 115mm deep starter block + (B) a 25mm

plasterboard and sealed space + (C) 75mm Gazco space

(part number 8315) with a marble slip or similar, inserted

behind the spacer front flange, see diagram 1.

Or the total depth can be achieved by using a deeper starter

block, remedial building work to the front of the fireplace

opening, and a marble slip or similar, or a combination of this.

NEvER PlASTER DIRECT TO ThE FACE OF A PRECAST

FlUE. USE ADhESIvE TO FIX ThE PlASTERBOARD TO ThE

FACE OF ThE FlUE AND FINAllY SkIM ThE

PlASTERBOARD.

1

A = Minimum precast flue starter block depth (115mm).

B = Plasterboard and adhesive seal all around fire opening.

C = Gazco spacer (8315)

D = Minimum total depth including 25mm for debris.

A

B C

D

Hearth level

AR1217

When fitting the Logic Convector fire and a Stovax Cast Iron

Convector fireplace to a precast letter box flue with a

standard starter block, the 8315 spacer kit will be required,

together with an extra deep 142mm rebate surround.

The Combination Convector breast. Fireplace requires a

75mm stud-work chimney breast.

The appliance can also be fitted into a metal flue box with a

5” (125mm) diameter flexible liner. In this installation a 1”

(25mm) rebated fire surround must be used. Refer to

diagram 2 for dimensions.

Class 1 flues. Chimneys over 9” x 9” must be lined.

A flue restrictor is provided with the Logic convector. This

must be fitted when the flue is 9” x 9” or when the flue pull

is excessive. This is fitted from inside the appliance across the

outlet at the top of the convector box with two screws

provided.

1.2 The minimum effective height of the flue or chimney must

be 3 m (10ft).

1.3 The chimney or flue must be free from any obstruction.

Any damper plates should be removed or secured in the

fully open position, and no restrictor plates should be fitted.

1.4 The chimney should be swept immediately prior to the

installation of the appliance - unless it can be seen to be

clean and unobstructed throughout its entire length.

1.5 Ensure that there is a smooth taper transition from the

fireplace opening into the chimney or flue.

1.6 The flue pull should be checked prior to installation of the

appliance. Apply a smoke pellet to the flue or chimney

opening and ensure that the smoke is drawn into the

opening. If there is not a definite flow, preheat the chimney

for a few minutes and re-test the flow.

IF ThERE IS STIll NO DEFINITE FlOW, ThE ChIMNEY

MAY REQUIRE ATTENTION - SEEk EXPERT ADvICE.

2. APPlIANCE lOCATION

2.1 This appliance must stand on a non-combustible hearth

that is at least 12mm thick and 50mm thick at least at the

periphery.

2.2 It must be fitted into a non-combustible opening.

2.3 These appliances must be hearth mounted into a fireplace

opening conforming to National Standards. The minimum

dimensions shall be as shown in diagram 2.