Optional accessories, Factory setpoints – Greenheck Fan HEAT RECOVERY UNIT WITH EVAPORATIVE COOLING HRE-20 User Manual
Page 21

21
S1 to SN contact for On/Off
A1 (0-10VDC) referenced to AC (Can use +15 VDC from +V)
Parameter
Setting
A1-01
Access Level
2
C6-02
Carrier frequency
2
d2-02
Ref Lower Limit
50%
E2-01
Motor Rated FLA
Motor FLA
H3-03
Terminal A1 Bias
50%
O2-03
User Defaults
1
A1-01
Access Level
0
S1 to SC contact for On/Off
FR (0-10VDC) referenced to FC (Can use +12 VDC from FS)
Parameter
Setting
n01
Access Level
1
n31
Ref Lower Limit
50%
n32
Motor Rated FLA
Motor FLA
n40
Multi-Function output (MA,MB,MC)
0
n42
Analog Freq . Reference Bias
50%
n46
Carrier Frequency
2
n01
Access Level
0
Factory Setpoints -
MODULATING CONTROL (0-10 VDC) FOR FAN SPEED
Yaskawa E7 Drive
Yaskawa GPD-305 Drive
OPTIONAL ACCESSORIES
Variable frequency drives (VFD) for the blowers are factory setup to receive a 0-10 VDC signal wired in the field
(refer to previous page for terminal locations) . Most of the setpoints in the VFDs are factory defaults . There are
a few, though, that are changed at Greenheck and are shown in the tables below . To gain access to change
setpoints on the E7 drive, parameter A1-01 needs to be set at “2” . To gain access to change setpoints on the GPD-
305 drive, parameter n01 needs to be set at “1” . To prevent access on either drive, change the parameter to “0” .
Factory Setpoints -
MULTI-SPEED CONTROL (1/3 OR 1/2 SPEED REDUCTION) FOR FAN SPEED
S1 to SN contact for On/Off
Parameter
Setting
A1-01
Access Level
2
b1-01
(Frequency) Reference Source
0
C6-02
Carrier frequency
2
d1-01
Frequency Reference 1
60
d1-02
Frequency Reference 2
40
d1-03
Frequency Reference 3
30
d1-04
Frequency Reference 4
60
E2-01
Motor Rated FLA
Motor FLA
O2-03
User Defaults
1
A1-01
Access Level
0
Yaskawa E7 Drive
S1 to SC contact for On/Off
Parameter
Setting
n01
Access Level
1
n03
Reference Selection
1
n21
Frequency Reference 1
60Hz
n22
Frequency Reference 2
40Hz
n23
Frequency Reference 3
30Hz
n24
Frequency Reference 4
60Hz
n32
Motor Rated FLA
Motor FLA
n38*
Multi-function Input Sel 4 (Term S4)
6
n39*
Multi-function Input Sel 5 (Term S5)
7
n40
Multi-Function output (MA,MB,MC)
0
n46
Carrier Frequency
2
n01
Access Level
0
*Parameter n39 must be set to 7 before n38 can be set to 6 (the
drive does not allow these parameters to be the same number, n39
default is 6)
Yaskawa GPD-305 Drive
Variable Frequency Drives for
Energy Recovery Wheel
Factory installed VFD for the energy recovery wheel are programmed at the factory per the settings shown
below . Refer to the instruction manual that ships with the unit when making adjustments . A copy of the manual
can be found online at www .drives .com . For technical support, contact Yaskawa direct at 1-800-927-5292 .
Parameter
Setting
n01
Access Level
1
n30
Ref Upper Limit
100% or 66%*
n32
Motor Rated FLA
Motor FLA
n33
Elect Thermal Overload
1
n36
Multi-Function input (terminal S2)
10
n40
Multi-Function output (MA,MB,MC)
4
n41
Analog Freq . Reference Gain
0
n42
Analog Freq . Reference Bias
99
n46
Carrier Frequency
2
n58
Frequency Detection Level
20
n01
Access Level
0
Yaskawa GPD-305 Drive
*36 inch wheel is 66% (40Hz) . All other wheels are 100% (60Hz) .