1-20
SPARC Enterprise M4000/M5000 Servers Overview Guide • December 2010
1.3.6
Operator Panel
The operator panel (
), which is not redundant, displays the system status,
system problem alerts, and location of system faults. It also stores the system
identification and user setting information. For more information on the operator panel
functions, refer to the SPARC Enterprise M4000/M5000 Servers Service Manual.
TABLE 1-7
CPU Types and Maximum Power Consumption on the M4000 Server
*
* M4000 system configuration: CPUM x 2, MEMB x 4, 8GB DIMM x 32, HDD x 2, PCIe x 4, PCI-X x 1, DAT x 1.
CPU Type
Frequency (GHz)
Number
Power
Consumption (W)
Apparent
Power (VA)
Heat Dissipation (KJ/h)
SPARC 64 VI processor
2.15
4
1556
1621
5602
SPARC 64 VII processor
2.4/2.53
4
1656
1725
5962
SPARC 64 VII+ processor
2.66
4
1692
1763
6091
TABLE 1-8
CPU Types and Maximum Power Consumption on the M5000 Server
*
* M5000 system configuration: CPUM x 4, MEMB x 8,8GB DIMM x 64, HDD x 4, PCIe x 8, PCI-X x 1, DAT x 1.
CPU Type
Frequency (GHz)
Number
Power
Consumption (W)
Apparent
Power (VA)
Heat Dissipation (KJ/h)
SPARC 64 VI processor
2.15
8
2998
3123
10793
SPARC 64 VII processor
2.4/ 2.53
8
3198
3331
11513
SPARC 64 VII+ processor
2.66
8
3270
3406
11772