Installation Guide

69-1922EFS—01

6

ENGLISH

1

0

Done

Next

M29387

To begin, press and hold the

s

and FAN

buttons until the display changes.

Function

number

Setting

Press

s

or

t

to change settings.

Press NEXT to advance to the next function.

Press DONE to exit and save settings.

Installer setup

Follow the procedure below to configure the thermostat to match the installed
heating/cooling system, and customize feature operation as desired.

Continued on next page

Setup function

Settings & options (factory default in bold)

Shaded areas below apply only to

TH5320U/TH5220D

or as otherwise noted.

*[Other cycle rate options: 2, 4, 6, 7, 8, 10, 11 or 12 CPH]

1

System type

0

1 heat/1 cool conventional

1

1 heat/1 cool heat pump (no aux. heat)

2

Heat only — 2-wire systems, 3-wire zone valves (Series 20), and

normally open zone valves

3

Heat only with fan

4

Cool only

5

2 heat/1 cool heat pump (with aux. heat)

6

2 heat/2 cool conventional

7

2 heat/1 cool conventional

8

1 heat/2 cool conventional

9

2 heat/2 cool heat pump (no aux. heat) -

TH5320U

only

10 3 heat/2 cool heat pump (with aux. heat) -

TH5320U

only

2

Changeover valve

(O/B terminal)

0

Changeover valve (O/B terminal energized in cooling)

1

Changeover valve (O/B terminal energized in heating)

3

Fan control

(heating)

0

Gas or oil furnace — equipment controls fan in heating

1

Electric furnace — thermostat controls fan in heating

5

Stage 1 heat cycle

rate (CPH: cycles/hour)*

5

For gas or oil furnaces of less than 90% efficiency

1

For steam or gravity systems

3

For hot water systems & furnaces of over 90% efficiency

9

For electric furnaces

6

Stage 2 heat cycle

rate/Auxiliary heat

cycle rate (CPH)*

5

For gas or oil furnaces of less than 90% efficiency

1

For steam or gravity systems

3

For hot water systems & furnaces of over 90% efficiency

9

For electric furnaces

7

Auxiliary heat cycle

rate (CPH)*

Only

TH5320U

for 3H/2C Heat Pumps

5

For gas or oil furnaces of less than 90% efficiency

1

For steam or gravity systems

3

For hot water systems & furnaces of over 90% efficiency

9

For electric furnaces

8

Emergency heat cycle

rate (CPH)*

9

For electric emergency heat

1

For steam or gravity systems

3

For hot water systems & furnaces of over 90% efficiency

5

For gas or oil furnaces of less than 90% efficiency