Wiring

Wiring guide — conventional systems

Shaded areas below apply only to

TH5320U/TH5220D

or as otherwise noted.

1H/1C System

(1 transformer)

Rc

Power

[1]

R

[R+Rc joined by jumper]

Y

Compressor contactor

C

24VAC common

[3]

W

Heat relay

G

Fan relay

Heat-only System

Rc

Power

[1]

R

[R+Rc joined by jumper]

C

24VAC common

[3]

W

Heat relay

Heat-only System

(Series 20)

[5]

Rc

[R+Rc joined by jumper]

R

Series 20 valve terminal “R”

[1]

Y

Series 20 valve terminal “W”

C

24VAC common

[3]

W

Series 20 valve terminal “B”

Heat-only System

(normally open zone valve)

[5]

Rc

[R+Rc joined by jumper]

R

Power

[1]

Y

Normally open zone valve

C

24VAC common

[3]

1H/1C System

(2 transformers)

Rc

Power (cooling transformer)

[1, 2]

R

Power (heating transformer)

[1, 2]

Y

Compressor contactor

C

24VAC common

[3, 4]

W

Heat relay

G

Fan relay

Heat-only System

with Fan

Rc

Power

[1]

R

[R+Rc joined by jumper]

C

24VAC common

[3]

W

Heat relay

G

Fan relay

Cool-only System

Rc

Power

[1]

R

[R+Rc joined by jumper]

Y

Compressor contactor

C

24VAC common

[3]

G

Fan relay

2H/2C System

(1 transformer)

[6]

Rc

Power

[1]

R

[R+Rc joined by jumper]

Y

Compressor contactor (stage 1)

C

24VAC common

[3]

W

Heat relay (stage 1)

G

Fan relay

W2

Heat relay (stage 2)

Y2

Compressor contactor (stage 2)

2H/2C System

(2 transformers)

[6]

Rc

Power (cooling transformer)

[1, 2]

R

Power (heating transformer)

[1, 2]

Y

Compressor contactor (stage 1)

C

24VAC common

[3, 4]

W

Heat relay (stage 1)

G

Fan relay

W2

Heat relay (stage 2)

Y2

Compressor contactor (stage 2)

See

[notes]

below

Rc

Y

W

G

R

C

M29372

Rc

W

R

C

M29373

Rc

Y

W

R

C

M29374

Rc

Y R

C

M29375

Rc

Y

W

G

R

C

M29376

Rc

W

G

R

C

M29377

Rc

Y

G

R

C

M29378

Rc

Y

W

G

W2

Y2

R

C

M29379

Rc

Y

W

G

W2

Y2

R

C

M29380

NOTES

Wire specifications:

Use 18- to 22-gauge thermostat wire.

Shielded cable is not required.

[1]

Power supply. Provide disconnect means

and overload protection as required.

[2]

Remove jumper for 2-transformer systems.

[3]

Optional 24VAC common connection.

[4]

Common connection must come from

cooling transformer.

[5]

In Installer Setup, set system type to

Heat Only.

[6]

In Installer Setup, set system type to

2Heat/2Cool Conventional.

[7]

In Installer Setup, set changeover valve to

O or B.

[8]

In Installer Setup, set system type to

2Heat/1Cool Heat Pump.

[9]

In Installer Setup, set system type to

2Heat/2Cool Heat Pump.

[10]

In Installer Setup, set system type to

3Heat/2Cool Heat Pump.

[11]

L terminal sends a continuous output when

thermostat is set to Em. Heat. Connect

to Honeywell zoning panels to switch the

panel to Emergency Heat.

[12]

Install field jumper between Aux and E if

there is no emergency heat relay.