MICROTEL Series 1000EX Dialer
33
z I/O Channel Type
*cc2*
Report I/O channel c TYPE
**cc2nn*
Program I/O channel c TYPE
**cc208Cv*
Program I/O channel c to Follow Channel C’s Value
Selection of I/O channel type (cc = 01 to 41 for I/O channels starting at leftmost
slot).
N Setting
Meaning
00
SPARE
No Type Selected
01
Digital Input Normally Open
Contact closure Normally Open
02
Digital Input Normally Closed
Contact closure Normally Closed
03
Digital Output
Digital Output that is user definable to
be Open or Closed
04
Analog Output (00.0 - 99.9%)
Analog Output that is user definable to
be at some setting
05
Analog Input (00.0 - 99.9%)
Current Percentage of an input value
06
Local Alarm Output
Digital Output that Closes when there
is a local alarm
08
Follow Channel Output
Digital Output that Closes depending
on the followed channel’s state
(see below)
Example- Command:
**03201*
Response: Channel three type is one normally open digital input.
NOTE: When
using
Digital or Analog Outputs, see the section labeled Site
Control.
**cc208CCV*
Program I/O channel c to Follow Channel C’s Value
Value Setting
Meaning
CC
Followed Channel (01-41)
The I/O Channel whose channel
status is being followed.
V
Type of Follow Channel (1-5)
0) Digital Output Follow Channel
1) Dout Follow Channel Status
2) Dout Follow Channel Alarm
3) Dout Follow Fill Algorithm
4) Dout Follow Empty Algorithm
The condition that this Output
Channel is following.
Example- Command:
**04208032*
Response:
Channel four type is eight digital output following channel three