Remote panel troubleshooting chart – FloAire Compact Direct Fired Heater User Manual

Page 25

background image

25

Remote Panel Troubleshooting Chart

Light Indication

Condition

Possible Cause

No Lights

Power not available to Remote Panel

Bad voltage to unit
Main disconnect in “OFF” Position
Circuit breaker tripped
Bad main transformer

POWER Light Only

Proper unit Off Operation

No problem

No power to motor starter

Manual/Off/Auto Switch in “Off” Position
(3 Position Remote Panels Only)
Improper damper function
Low Temperature Thermostat Timed
Out (Option)

POWER Light and
BLOWER ON Light

Proper Ventilation Operation

No Problem

No Power to Flame Safety Controller

Manual/Off/Auto Switch in “Off” Position
(2 Position Remote Panels Only)
Heat/Vent Switch in “Vent” Position
High Temperature Limit Thermostat
Tripped
Manual/Off/Auto Switch in “Auto”
Position and Intake Air Thermostat not
Satisfied
Insufficient Airflow

Improper Airflow

Excessive Airflow
Bad airflow switch
Problem with air probes
Problem with airflow tubing
Broken Belt
Filters Dirty or Need Replacement

POWER Light and
BLOWER ON Light and
BURNER ON Light

Proper Heating Operation

No Problem