beautypg.com

FloAire Compact Direct Fired Heater User Manual

Page 15

background image

15

Adjust pilot flame.

Lock unit into

high fire.

Adjust

incoming gas

pressure.

Does high fire produce

at least a 70°F temp

rise and produce the

correct manifold

pressure?

Adjust high fire

No

Lock unit into low fire.

Yes

Does thin flame fill

entire burner length?

Adjust low

fire.

Setting incoming pressure:
Presure must be measured at first "T" in
supply gas line before the first gas valve.

Adjusting the pilot:
To adjust the pilot flame, remove the cap
from the pilot adjustment screw on the
combination gas valve. Increase the pilot
gas flow by turning the screw counter-
clockwise. Decrease the pilot gas flow by
turning the screw clockwise.

Adjusting high fire:
High fire manifold pressure should be 5"
maximum for natural gas and 2.5"
maximum for propane. High fire should
produce at least a 70°F temperature rise.
Remove wire #4 from the Maxitrol 14
amplifier (#2 and #4 for Maxitrol 44). This
will drive the valve into its full open
position. Adjust high fire with the
regulator inside the unit. Turn clockwise
to increase temperature rise. Replace the
wires on the Maxitrol Amplifier.

Adjusting low fire:
Remove wire #5 from the Maxitrol 14
amplifier (#8 for Maxitrol 44). This will
drive the valve into its lowest position.
Adjust the low fire by turning the low fire
bypass screw on the side of the M411
modulating valve. Refer to the included
Maxitrol literature for more detailed
information. Ensure that the enite length
of burner is filled with a thin flame.

Yes

No

No

Burner start up

complete.

Yes

Is incoming gas pressure

5"-14"?

Heater Start Up Summary