12

Fan to Building Wiring Connection

OPERATION

Prior to starting up or operating the heater, check all fasteners for tightness. In particular, check the set
screw in the wheel hub, bearings and the fan sheaves (pulleys). With power and gas to the heater OFF or
prior to connecting ventilator to power, turn the fan wheel by hand to be sure it is not striking the inlet or
any obstacles. Re-center if necessary.

Start Up

Special Tools Required

AC Voltage Meter

Tachometer

Standard Hand Tools

Amperage Meter

Manometer

Differential Pressure Gauge

Start Up Procedure

1. Check all electrical connections for tightness and continuity.
2. Check pulley alignment and belt tension as described below.
3. Inspect the condition of the intake damper and damper linkage, if provided.
4. Inspect the air-stream for obstructions and install intake filters if missing.
5. Compare the supplied motor voltage with the fan’s nameplate motor voltage. If this does not

match, correct the problem.

6. Start the fan up, by turning the external disconnect to the ON position, and shut it OFF

immediately to check rotation of the wheel with the directional arrow on the blower scroll.
Reversed rotation will result in poor air performance, motor overloading and possible burnout.
For units equipped with a single-phase motor check the motor wiring diagram to change rotation.
For 3-phase motors, any two power leads can be interchanged to reverse motor direction.

7. When the fan is started up, observe the operation and check for any unusual noises.