beautypg.com

Kistler-Morse KM STXPlus User Manual

Page 48

background image

APPENDIX B: KISTLER-MORSE

®

PROTOCOL SERIAL COMMANDS

Request from Master

Response from STXplus

>aaK2ssr

A000000dssr

Format

>01K2DEr

A000000050r

Example

‘L2’ Command — Write AB-RIO Baud Rate
This command is sent by the master to set the AB-RIO baud rate of an STXplus. The range of
acceptable values is 0-2 where 0 for 57.6K, 1 for 115.2K, or 2 for 230.4K. For this example, the
master sets AB-RIO baud rate for an STXplus at address 01 to 1 (115.2K). Any of the 6 leading
zeros may be omitted.

Request from Master

Response from STXplus

>aaL2000000dssr

Ar

Format

>01L2110r

Ar

Example

‘K3’ Command — Read AB-RIO Address
This command is sent by the master to request the STXplus to send the AB-RIO address. The
range of acceptable values is 0-255. For this example, the master requests AB-RIO address for
an STXplus at address 01 which returns 57 and a checksum of 5C.

Request from Master

Response from STXplus

>aaK3ssr

A0000dddssr

Format

>01K3DFr

A00000575Cr

Example

‘L3’ Command — Write AB-RIO Address
This command is sent by the master to set the AB-RIO address of an STXplus. The range of
acceptable values is 0-255. For this example, the master sets AB-RIO address for an STXplus at
address 01 to 12. Any of the leading zeros may be omitted.

Request from Master

Response from STXplus

>aaL30000dddssr

Ar

Format

>01L31243r

Ar

Example

‘K4’ Command — Read AB-RIO Group
This command is sent by the master to request the STXplus to send the AB-RIO group. The
range of acceptable values is 0-3 where 0 for Group 0, 1 for Group 2, 2 for Group 4, or 3 for
Group 6. For this example, the master requests AB-RIO group for an STXplus at address 01
which returns 3 (Group 6) and a checksum of 53.

Request from Master

Response from STXplus

>aaK4ssr

A000000dssr

Format

>01K4DEr

A000000353r

Example

‘L4’ Command — Write AB-RIO group
This command is sent by the master to set the AB-RIO group of an STXplus. The range of
acceptable values is 0-3 where 0 for Group 0, 1 for Group 2, 2 for Group 4, or 3 for Group 6. For
this example, the master sets AB-RIO group for an STXplus at address 01 to 1 (Group 2). Any of
the 6 leading zeros may be omitted.

B-29