beautypg.com

Kistler-Morse KM STXPlus User Manual

Page 43

background image

APPENDIX B: KISTLER-MORSE

®

PROTOCOL SERIAL COMMANDS

‘PI’ Command — Write Setpoint Deadband Value
This command is sent by the master to set the setpoint deadband value of an STXplus.
Acceptable values for setpoint number is 1 and 2. The range of this value can be between 0 and
2,147,483,647. For this example, the master sets setpoint 2’s deadband value for an STXplus at
address 01 to 1.1219 assuming it is using a format of 6(X.XXXX).

Request from Master

Response from STXplus

>aaPIn(-)ffffffffssr

Ar

Format

>01PI21.121958r

Ar

Example

‘G8’ Command — Read Setpoint Fail-safe Mode
This command is sent by the master to request the STXplus to send the setpoint fail-safe mode.
Acceptable values for setpoint number is 1 and 2. The range of acceptable values is 0-2 where
0 is no change, 1 is setpoint off, or 2 is setpoint on. The default value is 0 (no change). For this
example, the master requests setpoint 2’s fail-safe mode for an STXplus at address 01 which
returns 0 (no change) and a checksum of 51.

Request from Master

Response from STXplus

>aaG8nssr

A000000dssr

Format

>01G8212r

A000000151r

Example

‘P8’ Command — Write Setpoint Fail-safe Mode
This command is sent by the master to set the setpoint failsafe mode of an STXplus.
Acceptable values for setpoint number is 1 and 2. The range of acceptable values is 0-2 where
0 is no change, 1is setpoint off, or 2 is setpoint on. For this example, the master sets setpoint 1’s
fail-safe mode for an STXplus at address 01 to 1 (setpoint off). Any of the 6 leading zeros may
be omitted.

Request from Master

Response from STXplus

>aaP8n000000dssr

Ar

Format

>01P8114Br

Ar

Example

‘G9’ Command — Read Setpoint High/Low Mode
This command is sent by the master to request the STXplus to send the setpoint high/low mode.
Acceptable values for setpoint number is 1 and 2. The range of acceptable values is 0-1 where
0 is low mode or 1 is high mode. The default value is 0 (low mode). For this example, the master
requests setpoint 1’s high/low mode for an STXplus at address 01 which returns 0 (low mode)
and a checksum of 50.

Request from Master

Response from STXplus

>aaG9nssr

A000000dssr

Format

>01G9112r

A000000050r

Example

B-24