Kistler-Morse KM STXPlus User Manual
Page 43
APPENDIX B: KISTLER-MORSE
®
PROTOCOL SERIAL COMMANDS
‘PI’ Command — Write Setpoint Deadband Value
This command is sent by the master to set the setpoint deadband value of an STXplus.
Acceptable values for setpoint number is 1 and 2. The range of this value can be between 0 and
2,147,483,647. For this example, the master sets setpoint 2’s deadband value for an STXplus at
address 01 to 1.1219 assuming it is using a format of 6(X.XXXX).
Request from Master
Response from STXplus
>aaPIn(-)ffffffffssr
Ar
Format
>01PI21.121958r
Ar
Example
‘G8’ Command — Read Setpoint Fail-safe Mode
This command is sent by the master to request the STXplus to send the setpoint fail-safe mode.
Acceptable values for setpoint number is 1 and 2. The range of acceptable values is 0-2 where
0 is no change, 1 is setpoint off, or 2 is setpoint on. The default value is 0 (no change). For this
example, the master requests setpoint 2’s fail-safe mode for an STXplus at address 01 which
returns 0 (no change) and a checksum of 51.
Request from Master
Response from STXplus
>aaG8nssr
A000000dssr
Format
>01G8212r
A000000151r
Example
‘P8’ Command — Write Setpoint Fail-safe Mode
This command is sent by the master to set the setpoint failsafe mode of an STXplus.
Acceptable values for setpoint number is 1 and 2. The range of acceptable values is 0-2 where
0 is no change, 1is setpoint off, or 2 is setpoint on. For this example, the master sets setpoint 1’s
fail-safe mode for an STXplus at address 01 to 1 (setpoint off). Any of the 6 leading zeros may
be omitted.
Request from Master
Response from STXplus
>aaP8n000000dssr
Ar
Format
>01P8114Br
Ar
Example
‘G9’ Command — Read Setpoint High/Low Mode
This command is sent by the master to request the STXplus to send the setpoint high/low mode.
Acceptable values for setpoint number is 1 and 2. The range of acceptable values is 0-1 where
0 is low mode or 1 is high mode. The default value is 0 (low mode). For this example, the master
requests setpoint 1’s high/low mode for an STXplus at address 01 which returns 0 (low mode)
and a checksum of 50.
Request from Master
Response from STXplus
>aaG9nssr
A000000dssr
Format
>01G9112r
A000000050r
Example
B-24