SPECIFICATIONS
Magic-Pak: HW/HWC
2-20
SRM-HW/HWC 2/99
5.
The
circulating air blower
shuts off approximately
90 seconds after
G
terminal on the
blower control
board
is de-energized (see note below).
FAN ON
Low Voltage
1.
When the switch on the
thermostat
is moved to the
“FAN ON” position, a 24-volt signal is sent to
G
.
2.
With
G
energized, the
blower control board
starts
a countdown to fan “on”. After approximately 15
seconds, the fan starts (see note below).
3.
The
blower control board
closes a relay on the
board, sending line voltage to the terminal marked
COOL
on the board. This starts the
circulating air
blower
.
4.
When the switch at the
thermostat
is moved to the
“OFF” position, the 24-volt signal to the
blower
control board
is interrupted. With no signal at the
G
terminal, the
blower control board
starts a
countdown to fan “off”. Approximately 90 seconds
later, a relay on the
blower control board
opens
(see note below). This interrupts the power to and
stops the
circulating air blower
.
Note:
Heatcraft
blower control boards have a
G
“on”
delay of 15 seconds and an “off” delay of 90
seconds.
Tridelta
blower control boards have no
“on” time delay and a 60 -130 second “off” delay.