Innotech iSEA User Manual
Page 40
Innotech Service & Event Analyser Installation Instructions
Page 40
© Mass Electronics Pty Ltd 2011
Edition 3.1 dated 26.03.2014
Figure 3-33: Creation of Actual Points under Virtual Points
Figure 3-34: Creating Actual Points
Element
Function
Description
Addition
The point is added to the Virtual point total.
Subtraction
The point is subtracted from the Virtual point total.
Conversion
factor
Ranges between 1x10
10
and 1x10
9
. This factor is multiplied with
the Actual point value.
Connection ID
and Device ID
This is the Connection and Device IDs of your Actual Points.
Reset Options
Auto Reset Default Setting. Accumulates at the highest
received value from a point.
Manual Reset The user defines the maximum value of the
meter reset.
Can't Reset This setting shows the "Live Value" of the
meter. No Accumulation.
Reset Value
This column will show the maximum meter value of the point
at which it was reset.
Advanced
Click the symbol to view or reset the Accumulated Reset Total
for the point.
Table 3-6:
Elements of an Actual Point within a Virtual Point
8. To link an Actual Point to a Virtual Point, select the virtual point, then in the Actual Points
panel, left click on the text “Click To Add New Point”.
9. Enter the Connection ID, the Device ID and the Point Address as required in the appropriate
fields.