beautypg.com

Innotech iSEA User Manual

Page 40

background image

Innotech Service & Event Analyser Installation Instructions

Page 40

© Mass Electronics Pty Ltd 2011

Edition 3.1 dated 26.03.2014

Figure 3-33: Creation of Actual Points under Virtual Points

Figure 3-34: Creating Actual Points

Element

Function

Description

Addition

The point is added to the Virtual point total.

Subtraction

The point is subtracted from the Virtual point total.

Conversion

factor

Ranges between 1x10

10

and 1x10

9

. This factor is multiplied with

the Actual point value.

Connection ID

and Device ID

This is the Connection and Device IDs of your Actual Points.

Reset Options

Auto Reset Default Setting. Accumulates at the highest

received value from a point.

Manual Reset The user defines the maximum value of the

meter reset.

Can't Reset This setting shows the "Live Value" of the

meter. No Accumulation.

Reset Value

This column will show the maximum meter value of the point

at which it was reset.

Advanced

Click the symbol to view or reset the Accumulated Reset Total

for the point.

Table 3-6:

Elements of an Actual Point within a Virtual Point

8. To link an Actual Point to a Virtual Point, select the virtual point, then in the Actual Points

panel, left click on the text “Click To Add New Point”.

9. Enter the Connection ID, the Device ID and the Point Address as required in the appropriate

fields.