beautypg.com

3 terminator resistor settings, Terminator resistor settings – ICP DAS USA I-7540D User Manual

Page 15

background image

2.3

Terminator resistor settings

In order to minimize reflection effects on the CAN bus line, the CAN bus lines

have to be terminated at both ends by two terminal resistances. Based on the ISO
11898-2 spec, each terminal resistance is 120Ω (or between 108Ω~132Ω). The
length related resistance should have 70 mΩ/m. Users should check the
resistances of their CAN bus, before they install a new CAN network as figure 2-4.

Figure 2-4: Terminator resistor

Moreover, to minimize the voltage drop on long distance, the terminal

resistance should be higher than the value defined in the ISO 11898-2. Table 2-4
may be used as a reference.

Table 2-4: Relation between bus cable and length

Bus Cable Parameters

Bus

Length

(meter)

Length Related

Resistance

(mΩ/m)

Cross Section

(Type)

Terminal

Resistance

(Ω)

0~40 70

0.25(23AWG)~

0.34mm

2

(22AWG)

124 (0.1%)

40~300 <

60

0.34(22AWG)~

0.6mm

2

(20AWG)

127 (0.1%)

300~600 <

40

0.5~0.6mm

2

(20AWG)

150~300

600~1K <

20

0.75~0.8mm

2

(18AWG)

150~300

i-7540D CAN-Ethernet Gateway User’s Manual (Version 1.4, April/2008)

15