Hearth & Home Technologies Inc. • Cinch Pipe & Term Caps • 4033-900 Rev K • 05/05

8

Secure the Vent Sections

Vertical sections of pipe must be supported every 8 ft after
the 25 ft maximum unsupported rise. The vent support or
plumber’s strap (spaced 120° apart) may be used to do this
(see Figures 2.12 and 2.13).

Horizontal sections of vent must be supported every 5 ft with
a vent support or plumber’s strap.

D. Disassemble Vent Sections

To disassemble any two pieces of pipe, rotate either section
(see Figure 2.14), so that the seams on both pipe sections
are aligned (see Figure 2.15). They can then be carefully
pulled apart.

Figure 2.12 Securing Vertical Pipe Sections

Figure 2.13 Securing Horizontal Pipe Sections

Fire Risk
Explosion Risk
Asphyxiation Risk

Use vent run supports per installation
instructions.
Connect vent sections per installation
instructions
• Maintain all clearances to combustibles.
• Do NOT allow vent to sag below

connection point to appliance.

• Maintain specifi ed slope (if required).

Improper support may allow vent to sag or
separate.

WARNING

Figure 2.14 Rotate Seams for Disassembly

Figure 2.15 Align and Disassembly Vent Sections