Warning, B. facing material – Heat & Glo Fireplace CERONA-36 User Manual
Page 36

Heat & Glo • Cerona-36, Cerona-42 • 2106-900 Rev. H • 11/08
36
B. Facing Material
Fire Risk.
Finish all edges and fronts to clearances and
specifi cations listed in manual.
• Black metal appliance front may be covered with
noncombustible material only.
• Do NOT overlap combustible materials onto appliance
front.
• Install combustible materials only up to specified
clearances on top, front and side.
• Seal joints between the fi nished wall and appliance top
and sides using only a 300º F minimum sealant.
Fire Risk.
Do NOT obstruct air inlet or outlet grilles.
Do NOT modify grilles.
• Modifying or covering grilles could cause
temperature rise and fi re hazard.
Finishing materials must not interfere with:
• Air fl ow through grilles or louvers.
• Operation of louvers or doors.
• Access for service.
Risk of Fire
• Non-combustible clearances MUST be
maintained.
• Sheetrock, wood or other combustibles must
NOT be used as sheathing or facing in the
non-combustible zone.
• See Section 11 for proper clearances.
• See Section 1 for combustible/non-
combustible defi nitions.
WARNING
WARNING
WARNING
Figure 11.4
A
B
C
Cerona-36
in.
49
16-3/4
43-5/8
mm
1245
425
1108
Cerona-42
in.
45-1/4
16-3/4
50-5/8
mm
1149
425
1286
Note: If using the Apollo Mantel System, the appliance must
be raised 1-1/4 in. from fl oor.
A
B
1 in.
(25)
C
CEILING
COMBUSTIBLE
SHEATHING
NON-COMBUSTIBLE
FACING MATERIAL
IN SHADED AREAS
FIREPLACE
ARCH OPENING
CLEARANCE
TO CEILING
MINIMUM
BOTTOM OF FIREPLACE
TO BOTTOM OF
NON-COMBUSTIBLE
FACING MATERIAL
Figure 11.3 Non-combustible Facing Material
A
B
Cerona-36
in.
43-5/8
50-3/16
mm
1108
1275
Cerona-42
in.
50-5/8
54-3/8
mm
1286
1381
A
B
NON-COMBUSTIBLE
FACING MATERIAL
1 in.
(25 mm)