Heat & Glo • Cerona-36, Cerona-42 • 2106-900 Rev. H • 11/08

27

D. Installing Heat Shield and Horizontal Termination Cap

Note: Where required, an exterior wall fl ashing is available.

When penetrating a brick wall, a brick extension kit is available
for framing the brick.

Heat Shield Requirements for Horizontal Termination

For all horizontally vented appliances, a heat shield MUST
be placed one inch above the top of the vent between the
wall shield fi restop and the base of the termination cap.

There are two sections of the heat shield. One section
is factory-attached to the wall shield fi restop. The other
section is factory-attached to the cap. See Figure 8.13.

If the wall thickness does not allow the required 1-1/2 inch
(38 mm) heat shield overlap when installed, an extended
heat shield (DVP-HSM-B) must be used.

Installing the Horizontal Termination Cap

Vent termination must not be recessed in the wall. Siding
may be brought to the edge of the cap base.

Flash and seal as appropriate for siding material at outside
edges of cap.

When installing a horizontal termination cap, follow the cap
location guidelines as prescribed by current ANSI Z223.1
and CAN/CGA-B149 installation codes.

Figure 8.13 Venting through the Wall

Burn Risk
• Local codes may require installation of a cap

shield to prevent anything or anyone from
touching the hot cap.

Fire Hazard

Impaired performance of appliance

• Telescoping flue section of termination cap

MUST be used when connecting pipe section
to termination cap.

• Maintain a 1-1/2 inch minimum overlap on

telescoping fl ue section of termination cap.

INTERIOR

HEAT SHIELD OR

EXTENDED

HEAT SHIELD

WALL SHIELD

FIRESTOP

HEAT SHIELD

1-1/2 IN. (38 MM) MIN.

OVERLAP

SHEATHING

VENT DEPTH FROM BACK OF APPLIANCE TO

OUTSIDE SURFACE OF EXTERIOR WALL

(SEE CHART BELOW)

SLIP SECTION

CAN BE EXTENDED

INNER VENT

OUTER VENT

EXTERIOR

Fire Risk
Exhaust Fumes Risk
Impaired Performance of Appliance
• Overlap pipe slip sections at least 1-1/2 inches.
• Use pilot holes for screws.
• Screws must not exceed 1 inch long.
• Pipe may separate if not properly joined.

WARNING

WARNING

WARNING

Important Notice: Heat shields may not be fi eld constructed.

The extended heat shield (DVP-HSM-B) may need to
be cut to length. You will attach the cut heat shield to
the existing cap heat shield or wall shield fi restop heat
shield (refer to Figure 8.13) using the supplied screws.
You MUST maintain a 1-1/2 in. (38 mm) overlap of the
extended heat shield and the existing shields (both ends
of the heat shield). The small leg on the extended heat
shield should rest on the top of the vent (pipe section) to
properly space it from the pipe section.

Cap Specifi cation Chart

(depth without using additional pipe sections)

Cerona-36
Cerona-42

DVP-TRAPK1

Top Vent

Depth

DVP-TRAP1

Rear Vent

Depth

DVP-TRAPK2

Top Vent

Depth

DVP-TRAP2

Rear Vent

Depth

2-1/2 in. to

4-3/8 in.

N/A

5 in. to 9 in.

N/A

DVP-HPC1

Top Vent

Depth

DVP-HPC1

Rear Vent

Depth

DVP-HPC2

Top Vent

Depth

DVP-HPC2

Rear Vent

Depth

2-1/2 in. to

4-5/8 in.

N/A

4-3/4 in. to

8-7/8 in.

N/A

DVP-TRAP1 can adjust 1-1/2 in. (3-1/8 to 4-5/8)

DVP-TRAP2 can adjust 4 in. (5-3/8 to 9-3/8)

DVP-HPC1 can adjust 2-1/8 in. (4-1/4 to 6-3/8)

DVP-HPC2 can adjust 4-1/8 in. (6-3/8 to 10-1/2)