Warning – Heat & Glo Fireplace CERONA-36 User Manual
Page 16
Heat & Glo • Cerona-36, Cerona-42 • 2106-900 Rev. H • 11/08
16
H
1
V
1
Figure 5.3
Figure 5.4
D. Vent Diagrams
1. Top Vent - Horizontal Termination
One Elbow
Two Elbows
INSTALLED
HORIZONTALLY
H
1
H
2
V
1
Fire Risk. Explosion Risk.
Do NOT pack insulation or other combustibles between ceiling fi restops.
• ALWAYS maintain specifi ed clearances around venting and fi restop systems.
• Install wall shield and ceiling fi restops as specifi ed.
Failure to keep insulation or other material away from vent pipe may cause fi re.
WARNING
V
1
Minimum
H
1
Maximum
Cerona-36 ONLY
1/2 ft
152 mm
2 ft
610 mm
1 ft
305 mm
2 ft
610 mm
2 ft
610 mm
5 ft
1.5 m
3 ft
914 mm
8 ft
2.4 m
4 ft
1.2 m
11 ft
3.4 m
5 ft
1.5 m
14 ft
4.3 m
6 ft
1.8 m
17 ft
5.2 m
7 ft
2.1 m
20 ft
6.1 m
8 ft
2.4 m
23 ft
7.0 m
V
1
= 40 ft. (12.2 m) Maximum
H
1
= 23 ft. (7.0 m) Maximum
V
1
+ H
1
= 63 ft. (19.2 m) Maximum
Note: Must have
a minimum verti-
cal vent before
attaching a 90º
elbow to the unit.
See chart.
Minimal Vertical Vent
Model
ft.
mm
Cerona-36
1/2
152
Cerona-42
1
305
V
1
Minimum
H
1
Maximum
Cerona-36 ONLY
1/2 ft
152 mm
2 ft
610 mm
1 ft
305 mm
2 ft
610 mm
2 ft
610 mm
5 ft
1.5 m
3 ft
914 mm
8 ft
2.4 m
4 ft
1.2 m
11 ft
3.4 m
5 ft
1.5 m
14 ft
4.3 m
6 ft
1.8 m
17 ft
5.2 m
7 ft
2.1 m
20 ft
6.1 m
8 ft
2.4 m
23 ft
7.0 m
V
1
+ H
1
+ H
2
= 63 ft. (19.2 m) Maximum
H
1
+ H
2
= 23 ft. (7.0 m) Maximum
Note: Must have
a minimum verti-
cal vent before
attaching a 90º
elbow to the unit.
See chart.
Minimal Vertical Vent
Model
ft.
mm
Cerona-36
1/2
152
Cerona-42
1
305