Chapter 3 – Parameter Setting Tables

Function mode

Code

Function name

Setting range

Initial data

remarks

C040

Overload advance notice
signal output mode

00(On accel. And decel, constant speed)/01(Only constant speed)

01

C041

Overload advance notice level

0.0-2.0*rated current(A)

Inverter

rated current

*C042

Frequency arrival setting for
acceleration.

0.00-99.99/100.0-400.0(Hz) 0.00

*C043

Arrival frequency setting for
deceleration.

0.00-99.99/100.0-400.0(Hz) 0.00

*C045

Frequency arrival setting for
acceleration 2.

0.00-99.99/100.0-400.0(Hz) 0.00

*C046

Arrival frequency setting for
deceleration 2.

0.00-99.99/100.0-400.0(Hz) 0.00

C055

Over torque level setting
(Forward-driving)

0.-200.(%)

100.

C056

Over torque level setting
(Reverse-regenerating)

0.-200.(%) 100.

C057

Over torque level setting
(Reverse-driving)

0.-200.(%) 100.

C058

Over torque level setting
(Forward-regenerating)

0.-200.(%) 100.

C061

Thermal warning level
setting

0.-100.(%) 80.

C062

Alarm code selection

00(Invalid)/01(3bit)/02(4bit)

00

*C063

Zero speed detection level
setting

0.00-99.99/100.(Hz) 0.00

C070 Data

command

02(operator)/03(RS485)/04(option1)/05(option2)

02

C071

Communicating transmission
speed

02(loop-back test)

03(2400bps)/04(4800bps)/05(9600bps)/06(19200bps)

04

C072

Communication code

1. -32.

1.

C073 Communication

bit

7(7bit)/8(8bit)

7

C074

Communication parity

00(no parity name)/01(even parity)/02(odd parity)

00

C075

Communication stop bit

1(bit)/2(bit)

1

C078

Communication waiting time

0.-1000.(ms)

0.

C081 O

adjustment

0.-9999./1000-6553(10000-65530)

Setting on

forwarding

C082 OI

adjustment

0.-9999./1000-6553(10000-65530)

Setting on

forwarding

C083 O2

adjustment

0.-9999./1000-6553(10000-65530)

Setting on

forwarding

C085

Thermistor adjustment

0.0 - 1000.

105.0

C086

AM offset adjustment

0.0 - 10.0(V)

0.0

C087

AMI adjustment

0. - 255.

80

C088

AMI offset adjustment

0. - 20.0(mA)

Setting on

forwarding

b034

RUN time/Power ON time level

0.-9999./1000-6553(10000-65530)hr

0.

b036

Start reduced voltage

00(Start reduced voltage time small)-06(Start reduced voltage time large)

06

b037

Display selection

00(all display)/01(each function display)/02(User setting / main setting)

00

b040

Torque limit mode selection

00(4 quadrant mode)/01(Terminal operation)/

02(Analog input)/03(Option1)/04(Option2)

00

b041

Torque limit level 1 setting
(Forward-driving at
4 quadrant mode)

0.-200.(%)/no(Invalid) 150.

b042

Torque limit level 2 setting
(Reverse-regenerating at
4 quadrant mode)

0.-200.(%)/no(Invalid) 150.

b043

Torque limit level 3 setting
(Reverse-driving at
4 quadrant mode)

0.-200.(%)/no(Invalid) 150.

b044

Torque limit level 4 setting
(Forward-regenerating at
4 quadrant mode)

0.-200.(%)/no(Invalid) 150.

b045 Torque

LAD-STOP

selection

00(Invalid)/01(Valid)

00

b046

Reverse run prevention
selection

00(Invalid)/01(Valid) 00

b080

AM adjustment

0. - 255.

180

b081

FM adjustment

0. - 255.

60

*b082 Start

frequency

adjustment

0.10-9.99(Hz)

0.10

b083

Carrier frequency setting

0.5-15.0(kHz) Derating enable, <0.5-10kHz>

5.0

b084

Initialize mode

00(Trip history clear)/01(Data initialization)/

02(Trip history clear + data initialization)

00

b086

Frequency scalar conversion
factor

0.1-99.9

1.0

b087

STOP key enable

00(valid)/01(invalid)

00

O

u

tput t

e

rm

inal s

tat

e s

e

tt

ing •

O

u

tput lev

e

l

s

e

tt

ing

C

o

m

m

u

ni

cati

on

functio

n

a

d

justm

e

n

t

A

n

a

log

me

te

r se

tt

ing

Miscel

laneou

s