3 extended function mode – Hitachi SJ700-2 Series User Manual
Page 8

1 - 4
1.2.3 Extended Function Mode
Default
Code
Function name
Monitored data or setting
_FF _FEF
_FUF
Note
A001
Frequency source setting
00 (keypad potentiometer) (*1), 01 (control circuit terminal block), 02 (digital
operator), 03 (RS485), 04 (option 1), 05 (option 2), 06 (pulse-string input), 07
(easy sequence), 10 (operation function result)
02 01 01
A002
Run command source setting
01 (control circuit terminal block), 02 (digital operator), 03 (RS485), 04 (option
1), 05 (option 2)
02 01 01
A003
Base frequency setting
30. to "maximum frequency " (Hz)
60.
50.
60.
A203
Base frequency setting, 2nd
motor
30. to "maximum frequency, 2nd motor" (Hz)
60. 50. 60.
A303
Base frequency setting, 3rd
motor
30. to "maximum frequency, 3rd motor" (Hz)
60. 50. 60.
A004
Maximum frequency setting
30. to 400. (Hz)
60.
50.
60.
A204
Maximum frequency setting, 2nd
motor
30. to 400. (Hz)
60. 50. 60.
Basic set
tings
A304
Maximum frequency setting, 3rd
motor
30. to 400. (Hz)
60. 50. 60.
A005
[AT] selection
00 (switching between O and OI terminals), 01 (switching between O and O2
terminals), 02 (switching between O terminal and keypad potentiometer) (*1),
03 (switching between OI terminal and keypad potentiometer) (*1), 04
(switching between O2 and keypad potentiometer) (*1)
00
A006
[O2] selection
00 (single), 01 (auxiliary frequency input via O and OI terminals)
(nonreversible), 02 (auxiliary frequency input via O and OI terminals)
(reversible), 03 (disabling O2 terminal)
03
A011
[O]-[L] input active range start
frequency
0.00 to 99.99, 100.0 to 400.0 (Hz)
0.00
A012
[O]-[L] input active range end
frequency
0.00 to 99.99, 100.0 to 400.0 (Hz)
0.00
A013
[O]-[L] input active range start
voltage
0. to "[O]-[L] input active range end voltage" (%)
0.
A014
[O]-[L] input active range end
voltage
"[O]-[L] input active range start voltage" to 100. (%)
100.
A015
[O]-[L] input active range start
frequency selection
00 (external start frequency), 01 (0 Hz)
01
A016
External frequency filter time
const.
1. to 30. or 31. (500 ms filter ±0.1 Hz with hysteresis)
31.
Analog input
and o
the
rs
A017
Easy sequence function
selection
00 (disabling), 01 (enabling)
00
A019
Multispeed operation selection
00 (binary: 16 speeds selectable with 4 terminals), 01 (bit: 8 speeds selectable
with 7 terminals)
00
A020
Multispeed frequency setting
0.0 or “start frequency” to “maximum frequency” (Hz)
0.00
A220
Multispeed frequency setting,
2nd motor
0.0 or “start frequency” to “maximum frequency, 2nd motor” (Hz)
0.00
A320
Multispeed frequency setting,
3rd motor
0.0 or “start frequency” to “maximum frequency, 3rd motor” (Hz)
0.00
A021
Multispeed 1 setting
0.0 or “start frequency” to “1st maximum frequency” (Hz)
0.00
A022
Multispeed 2 setting
0.0 or “start frequency” to “2nd maximum frequency” (Hz)
0.00
A023
Multispeed 3 setting
0.0 or “start frequency” to “3rd maximum frequency” (Hz)
0.00
A024
Multispeed 4 setting
0.0 or “start frequency” to “n-th maximum frequency” (Hz)
0.00
A025
Multispeed 5 setting
0.0 or “start frequency” to “n-th maximum frequency” (Hz)
0.00
A026
Multispeed 6 setting
0.0 or “start frequency” to “n-th maximum frequency” (Hz)
0.00
A027
Multispeed 7 setting
0.0 or “start frequency” to “n-th maximum frequency” (Hz)
0.00
A028
Multispeed 8 setting
0.0 or “start frequency” to “n-th maximum frequency” (Hz)
0.00
A029
Multispeed 9 setting
0.0 or “start frequency” to “n-th maximum frequency” (Hz)
0.00
A030
Multispeed 10 setting
0.0 or “start frequency” to “n-th maximum frequency” (Hz)
0.00
A031
Multispeed 11 setting
0.0 or “start frequency” to “n-th maximum frequency” (Hz)
0.00
A032
Multispeed 12 setting
0.0 or “start frequency” to “n-th maximum frequency” (Hz)
0.00
A033
Multispeed 13 setting
0.0 or “start frequency” to “n-th maximum frequency” (Hz)
0.00
A034
Multispeed 14 setting
0.0 or “start frequency” to “n-th maximum frequency” (Hz)
0.00
A035
Multispeed 15 setting
0.0 or “start frequency” to “n-th maximum frequency” (Hz)
0.00
A038
Jog frequency setting
"Start frequency" to 9.99 (Hz)
1.00
M
ult
ispeed ope
ra
tion
an
d jogging
A039 Jog
stop
mode
00 (free-running after jogging stops [disabled during operation]), 01
(deceleration and stop after jogging stops [disabled during operation]), 02 (DC
braking after jogging stops [disabled during operation]), 03 (free-running after
jogging stops [enabled during operation]), 04 (deceleration and stop after
jogging stops [enabled during operation]), 05 (DC braking after jogging stops
[enabled during operation])
00
.